4. Commissioning

4.3 Ignition

1. Turn the flue gas thermostat to 0 (Ignition) - except CBB 15 E.
2. Set the On/Off switch to 1.
3. Pull the lever to open the air flap.
4. Open the loading door.
5. Put some inflammable kindling with some paper on the bottom of
the combustion chamber. Leave a space of 2 to 4 cm between
the logs for the smoke to escape. Put in logs and light.
6. Close the loading door.

4.4 Adding more logs

Only add more logs if the previous load has been consumed to
at least 1/3 of the original volume.
1. Pull the lever to open the air flap.
2. Turn the flue gas thermostat to 0 (Ignition) - except CBB 15 E.
3. Wait for one minute and open the loading door.
4. Add logs to the combustion chamber.
5. Close the loading door.
6. Push the lever to close the air flap.
Set the flue gas thermostat between Min and Max (when in
operation) - except CBB 15 E.
10
7. When the wood is well lit (about 20-30 minutes later), continue to
fill the combustion chamber.
Close the loading door.
8. Push the lever to close the air flap.
9. Set the flue gas thermostat between Min and Max (when in
operation)*. The fan must continue to turn.
* except CBB 15 E.
When the fuel has been consumed, the fan is stopped by the
flue gas thermostat. This makes it possible to keep the embers
burning longer.
CBI-II / CBB 15 E