Adapting To Another Gas; Attaching The Label; Changing The Burner Injectors; Changing The Ignition Burner Injector - DeDietrich Elitec DTG 1304 Eco.NOx/V Technical Instructions

Gas-fired boilers
Table of Contents

Advertisement

Operations to be carried out to allow the change from H/E natural gas
to L/LL natural gas or to propane and vice versa.
The actions described below must be carried out by a
qualified technician.
Check the seals for the gas.

1 Attaching the label

This indicates the type of gas for which the burner is set.

2 Changing the burner injectors

Lift out the injector with a number 12 spanner assemble the new
injectors with their new joint.

3 Changing the ignition burner injector

.
Unscrew the connecting nut (14 spanner),
Pull the gas supply pipe towards yourself.
Take out the ignition burner nozzle.
Fit the new nozzle .
Re-attach the supply tube (14 spanner)
18

Adapting to another gas

Natural gas H/E
Natural gas L/LL
Natural gas H/E
Natural gas L/LL
Propane
Prior to re-assembling the injector for each burner also replace
the aluminium joint. First tighten the injectors by hand and
carefully lock them using a spanner.
Natural gas H/E
Natural gas L/LL
(France)
Natural gas L
(
Propane
France:The 40 mm ignition burner injection fitted in the factory
is suitable for operation on natural gas H/E and L/LL (no
conversion necessary for switching from H/E to L/LL and vice
versa).
DTG 1300 Eco.NOx/V
Conversion kits
Propane
Nozzle marking
210B
245B
140A
Nozzle marking
4
4
5
France)
3
Package GL34
8518-7007
Package GL31
8518-7004
Package GL32
8518-7005
Nozzle diameter
(mm)
2,10
2,45
1,40
Nozzle diameter
(mm)
0,40
0,40
0,50
0,30
23/06/05 - 300002940-001B