[46] First Communicator Option Code

Zone Light 1: Communicator Disabled / Enabled
ON: Communicator Disabled. The system's communicator will be shut off and events will not be transmitted to
the monitoring station.
• OFF: Communicator Enabled. The system's communicator will be enabled and all events with reporting codes
will be reported to the monitoring station. Refer to the Telephone Number, Reporting Code and Call
Direction Programming Sections.
Zone Light 2: Restorals Reporting Option
ON: Restorals on Bell Time-Out. Zone restoral reporting codes will not be transmitted until the zone has been
restored and the Bell Cut-off Time has expired. If the zone is still active when the Bell Cut-off Time
expires, the restoral will be transmitted when the zone restores or when the system is disarmed. Note that
24-Hour Zones will not restore until the zone is mechanically restored.
• OFF: Restorals Follow Zones. Zone restoral reporting codes will be transmitted when the zone is mechanically
restored. If zones are still active when the system is disarmed, the restoral codes will be transmitted when
the system is disarmed. Note that 24-Hour Zones will not restore until the zone is mechanically restored.
Zone Light 3: DTMF or Pulse Dialing
• ON: DTMF Dialing. The control panel will dial telephone numbers using DTMF (dual tone multi-frequency) dialing.
OFF: Pulse Dialing. The control panel will dial telephone numbers using pulse (rotary) dialing.
Zone Light 4: Transmission Back-up Options
• ON: Call First Telephone Number Only. When events programmed to report to the First Telephone Number
are to be transmitted, up to eight attempts will be made to communicate to the First Telephone Number.
If all eight attempts to communicate fail, a Failure to Communicate Trouble will be generated.
OFF: Back-up to Second Telephone Number. If eight attempts to communicate to the First Telephone Number fail,
up to eight attempts will be made to communicate to the Second Telephone Number. If all eight attempts to
communicate to the Second Telephone Number fail, a Failure to Communicate Trouble will be generated.
Zone Light 5: Partial Closing Identification Options
ON: Partial Closings Identified. The alarm codes for all manually bypassed zones will be transmitted after the
Partial Closing Code and before the Closing Access Code when the system is armed. NOTE: If "Partial
Close on Auto-Arm" is enabled (Section [08] Zone Light 4 ON), the alarm codes for all of the zones
force-armed by the Auto-Arming function will be transmitted after the Partial Closing Code and before the
User Closing Code.
• OFF: Partial Closings Not Identified. Manually bypassed zones will not be identified when the system is armed;
only the Partial Closing Code and the Closing Access Code will be transmitted.
Zone Light 6: Radionics Handshake Frequency Selection
ON: 1400Hz Handshake. The system will accept handshake tones at 1400Hz when using Radionics
communications formats.
• OFF: 2300Hz Handshake. The system will accept handshake tones at 2300Hz when using Radionics
communications formats. Consult with the monitoring station to determine which communication formats
and handshake frequencies are required.
Zone Light 7: Transmission Limit Reset Options
ON: Transmissions Limited to 24-hour Period. The Swinger Shutdown counter will be reset when the system
time changes from 23:59 (11:59 pm) to 00:00 (12:00 am).
• OFF: Transmissions Limited to Armed Period. The Swinger Shutdown counter will be reset when the system is
next armed. The Swinger Shutdown counter is used to limit the number of alarms each zone may transmit.
When a zone has generated the set number of alarms, any further alarms will be ignored and will not be
transmitted. When the Swinger Shutdown counter is reset, zones that had been "shut down" after
transmitting the set number of alarms will again be able to transmit alarms.