8-7-2. Mounting the UV unit
(1) Insert the UV unit into the joint section like the right
side figure.

8-8. Removing the Drain Pan (Air Outlet Ass'y)

Remove the hooks (1), (2) and (3) which secure the drain pan.
(1) Right side drain pan
Press the back right in the arrow direction, and the
hooked part can be released.
(2) Center part of the air outlet
Press the center part of the air outlet in the arrow
direction, and the tab can be released.
The center part of the air outlet may be removed
together with the right side drain pan when it is
removed.
Drain pan
35
Tab
Hole
Insulation material
UV unit
Tab