Fireplace Insert Installation
Hearth Requirements
Non-combustible hearth must extend 12" (300mm) in front of the insert and 4.625" (118mm) from
both sides of the insert
When installed over a timber floor:
Hearth must be a minimum of 75mm of non-
combustible masonry with 16mm of FC sheet
along with offcuts to provide air flow (see
illustration to the right).
NOTE: if using the "Lopi Flush Wood Zero
Clearance Box" (www.lopi.com.au) see the
instructions included with the zero clearance
box for hearth requirements.
When installed over a cement floor:
Hearth must be non-combustible.

Face Dimensions

Avalon Victorian Lace
33"

Drafting Performance

This appliance relies upon natural draft to operate. External forces, such as wind, barometric pressure,
topography, or factors of the home (negative pressure from exhaust fans, chimneys, air infiltration, etc.),
may adversely affect draft. Travis Industries can not be responsible for external forces leading to less
than optimal performance.