Start-Up; Check Heating Control - Carrier K Series Installation Instructions Manual

15.2+ seer2 2-stage packaged air conditioner and gas furnace system with r-410a refrigerant single and three phase 2-5 nominal tons sizes 24-60
Table of Contents

Advertisement

PGR5 Series K: Installation Instructions
4. Verify the following conditions:
a. Make sure gas line is free of air. Before lighting the unit for the
first time, perform the following with the gas valve in the OFF
position:
NOTE: If the gas supply pipe was not purged before connecting the
unit, it will be full of air. It is recommended that the ground joint union
be loosened, and the supply line be allowed to purge until the odor of gas
is detected. Never purge gas lines into a combustion chamber.
Immediately upon detection of gas odor, retighten the union. Allow 5
minutes to elapse, then light unit.
b. Make sure that outdoor-fan blade is correctly positioned in the
fan orifice.
c. Make sure that air filter(s) is in place.
d. Make sure that condensate drain trap is filled with water to
ensure proper drainage.
e. Make sure that all tools and miscellaneous loose parts have been
removed.

Start-up

CAUTION
!
FIRE, INJURY, OR DEATH HAZARD
Failure to follow this warning could result in property damage, personal
injury, or death.
Do not bypass any of the safety controls in the unit, including but not
limited to the main limit switch, rollout or burner rollout switch, and
pressure switch/pressure transducer.
Step 1 – Check for Refrigerant Leaks
WARNING
!
EXPLOSION HAZARD
Failure to follow this warning could result in
death, serious personal injury, and/or property
damage.
Never use air or gases containing oxygen for leak
testing or operating refrigerant compressors.
Pressurized mixtures of air or gases containing
oxygen can lead to an explosion.
Proceed as follows to locate and repair a refrigerant leak and to charge
the unit:
1. Locate leak and make sure that refrigerant system pressure has been
relieved and reclaimed from both high- and low-pressure ports.
2. Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened for
repair.
3. Add a small charge of R-410A refrigerant vapor to system and
leak-test unit.
4. Recover refrigerant from refrigerant system and evacuate to 500
microns if no additional leaks are found.
5. Charge unit with R-410A refrigerant, using an accurate scale. Refer
to unit rating plate for required charge.
Step 2 – Start-up Heating and Make Adjustments
Complete the required procedures given in the Pre-Start-Up section
before starting the unit. Do not jumper any safety devices when
operating the unit. Make sure that burner orifices are properly aligned.
Unstable operation my occur when the burner orifices in the manifold
are misaligned.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Follow the lighting instructions on the heating section operation label
(located on the inside of the control access panel) to start the heating
section.
NOTE: Make sure that gas supply has been purged, and that all gas
piping has been checked for leaks.
Pipe Plug
Fig. 11 – Burner Assembly
Fig. 12 – Monoport Burner

Check Heating Control

Start and check the unit for proper heating control operation as follows
(see furnace lighting instructions located on the inside of the control
access panel):
For 208/230 VAC Models:
1. Place room thermostat SYSTEM switch in the HEAT position and
the fan switch in AUTO position.
2. Set the heating temperature control setting several degrees higher
than the room temperature reading.
3. The induced-draft motor will always start on high speed for the
ignition sequence, regardless of the heating stage called.
4. After a pre-purge time of 15 sec with the induced-draft motor on
high speed, the sparker will be energized for 3-to-8 sec, and the gas
valve will be energized on low stage. If the burners do not light,
there is a 20-sec delay before another ignition attempt. If the
burners still do not light by the 4th consecutive ignition attempt,
there is a lockout. To reset the lockout, break the 24-v power to W1
and W2.
5. Once flame is established the integrated gas unit controller (IGC)
will look for 24-v power to W1 and W2. If there is 24-v power to
W1 only, the IGC will switch the induced-draft motor down to low
speed and maintain low stage on the gas valve. If there is 24-v
power to both W1 and W2, the IGC will maintain the induced-draft
motor on high speed and switch the gas valve to high stage.
15
Manifold
A07679
BURNER FLAME
BURNER
MANIFOLD
C99021

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pgr5 seriesHeil pgr536060kgp1g

Table of Contents