Appendix B Serial Converter Parameters; Parameter List - Allen-Bradley 1203-SSS User Manual

Powerflex smart self-powered serial converter
Hide thumbs Also See for 1203-SSS:
Table of Contents

Advertisement

Serial Converter Parameters
This chapter presents information about the parameters in the serial
converter.

Parameter List

No. Name and Description
01
[Adapter Port]
Port on the host product to which the serial converter is
connected.
02
[DF1 Addr Cfg]
DF1 node address for the serial converter. This is a
decimal value.
03
[DF1 Rate Cfg]
Serial port rate for the DF1 serial port on the serial
converter.
04
[Comm Flt Action]
Action that the serial converter and product take if the
serial converter detects that DF1 serial
communications are disrupted. This setting is effective
only if control I/O is transmitted through the serial
converter.
ATTENTION: Risk of injury or equipment damage exists. Parameter 04 -
[Comm Flt Action] lets you determine the action of the serial converter and
!
connected product if communications are disrupted. By default, this
parameter faults the product. You can set this parameter so that the product
continues to run. Precautions should be taken to ensure that the setting of
this parameter does not create a hazard of injury or equipment damage.
Appendix
Details
Default:
0
Minimum:
0
Maximum:
7
Type:
Read Only
Default:
1
Minimum:
0
Maximum:
254
Type:
Read/Write
Reset Required: Yes
Default:
0 = 9600
Values:
0 = 9600
1 = 19.2K
2 = 38.4K
Type:
Read/Write
Reset Required: Yes
Default:
0 = Fault
Values:
0 = Fault
1 = Stop (DPI) or
Fault (SCANport)
2 = Zero Data
3 = Hold Last
Type:
Read/Write
Reset Required: No