Quadra-Fire REMINGTON QFP40 Operation Manual page 37

Direct vent gas fireplace
Table of Contents

Advertisement

REMINGTON QFP40 Direct Vent FIREPLACE
HORIZONTAL INSTALLATION (CONT.)
Step 5. Slide the stove and vent assembly (see Fig. 9 below) towards the wall, carefully
inserting the vent pipe into the vent cap assembly. It is important that the vent
pipe extend into the vent cap sufficient distance so as to result in a minimum
pipe overlap of 1¼" (32mm). Secure the connection between the vent pipe and
the vent cap by attaching the two sheet metal strips extending from the vent cap
assembly into the outer wall of the vent pipe. Use the two sheet metal screws
provided to connect the strips to the pipe section. (Figure 9).
Note:
The attachment from the vent pipe to the vent cap must be siliconed. Venting
terminals shall not be recessed into a wall or siding.
FIG. 9
FOLD STRAP HERE
SHEET METAL SCREW
250-4721 JUNE 2001
WALL THIMBLE/CEILING
FIRESTOP AS REQUIRED BY
LOCAL JURISDICTION.
STRAP
Page 37