BUILDING CODES AND SAFETY STANDARDS

The design of this FIREPLACE has been tested and is listed with CSA INTERNATIONAL in
accordance with THE AMERICAN NATIONAL STANDARDS INSTITUTE - ANSI Z21.50. Latest
Edition, CSA Test Report No. 188842-1684324.
This manual serves only as a basic guideline for installation and use of this firebox and gas
piping. The complete installation must be in accordance with local codes and ordinances, or, in
the absence of local codes, with the American National Standards Institute National Fuel Gas
Code Z223.1 latest edition.
GENERAL INFORMATION
MODEL HD5030-TV IS A TOP-VENTED GAS FIREPLACE. IT IS DESIGNED TO BURN BY
DRAWING COMBUSTION AIR FROM THE ROOM THE UNIT IS INSTALLED IN AND/OR THE
OUTSIDE AIR KIT PROVIDED WITH THIS APPLIANCE.
THE EXHAUST FLUE GASES ARE TO BE VENTED THROUGH THE TOP-VENT USING 10"
B-TYPE GAS VENT PIPE.
THE CONTROL SYSTEM IS A MILLIVOLT TYPE THAT INCLUDES A ON-OFF SHUT-OFF
VALVE, A GAS CONTROL VALVE, A STANDING PILOT LIGHT ASSEMBLY, PIEZO IGNITOR
AND ON-OFF ROCKER SWITCH.
WARNING: THIS UNIT IS NOT FOR USE WITH SOLID FUEL.
NOTE: INSTALLATION AND REPAIR SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED
DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE
THAT THE UNITS CONTROL COMPARTMENT, BURNERS, AND CIRCULATING AIR
PASSAGE-WAYS BE KEPT CLEAN TO PROVIDE ADEQUATE COMBUSTION AND
VENTILATION AIR.
NOTE: B-Vent appliances are not designed to operate in negatively pressured environments
(pressure within the home is less than pressures outside). Significant negatively pressured
environments caused by weather, home design or other devices may impact the operation of
this appliance. Negative pressures may result in poor flame appearance, sooting, damage to
property and/or severe personal injury. Do not operate this appliance in negatively pressured
environments.
CLEARANCES REQUIRED
MINIMUM CLEARANCES FOR THE FIREBOX ARE:
1/2" ON THE SIDES AND BACK AND 0 AT THE BOTTOM. TOP CLEARANCE IS 1" WHICH
IS THE HEIGHT OF TOP STANDOFFS, SEE FIGURE 7.1 FOR FRAMING DIMENSIONS.
NOTE: PROVIDE ADEQUATE CLEARANCES AROUND AIR OPENINGS INTO THE
COMBUSTION CHAMBER.
NOTE: ADEQUATE ACCESSIBILITY CLEARANCES FOR SERVICING AND PROPER
OPERATION MUST BE PROVIDED IN ACCORDANCE WITH ANSI Z21.50. LATEST EDITION.