ELECTRICAL REQUIREMENTS AND
PRECAUTIONS
Y
our Hot Spring
spa to an improperly wired circuit will negate many of the spa's safety features. Please read and follow the electrical
installation requirements and instructions for your specific spa model completely!
SERVICE NOTE: All Hot Spring
has power to it, has a diagnostic function as well. It will begin blinking if the heater high limit thermostat has tripped. If the
power indicator light is blinking, follow the instructions in the troubleshooting section to identify and correct the cause. The
power indicator will stop blinking once the problem has been corrected.

230 VOLT PERMANENTLY CONNECTED MODELS

• Grandee
• Landmark
HOT SPRING
ELECTRICAL WORK SHOULD BE DONE BY AN EXPERIENCED, LICENSED ELECTRICIAN. WE RECOMMEND THE USE
OF APPROPRIATE ELECTRICAL CONDUIT, FITTINGS AND WIRE FOR ALL CIRCUITS.
An electrical subpanel containing two GFCI breakers is included with each 230 volt spa. We recommend that this subpanel
be used to supply power and protect the spa.
This subpanel requires a 50 amp, single phase, 230 volt, four wire service (two line, one neutral, one ground). The
grounding conductor must be at least the same gauge as the line conductors, but not less than #8 AWG. A minimum
#8 AWG solid copper bond wire is also required.
Mount the subpanel in the vicinity of the spa, but not closer than five feet away, in accordance with all local codes. (N.E.C.
680-6c)
INSTALLATION INSTRUCTIONS
1. To connect the electrical service, first remove the screws from the equipment compartment door. Carefully pull the
door panel away and down in order to remove it completely from the spa.
4. Connect the #12 AWG, White wire, from the subpanel 20 amp breaker, terminal N (load neutral) to TB-1, terminal 6.
NOTE: The white neutral wire must be attached to the LOAD neutral on the 230 volt, 20 amp breaker (not to the neutral
Electrical Requirements
®
Spa has been designed carefully to give you maximum safety against electrical shock. Connecting the
®
Spa models are equipped with a power indicator which, in addition to showing the spa
®
(Model G)
®
(Model S)
®
SPAS MUST BE WIRED IN ACCORDANCE WITH ALL APPLICABLE LOCAL ELECTRICAL CODES. ALL
Page 12
2. Locate the IQ 2000
Spa Control Box. Loosen
the screws on the front of the control box.
Remove the screws and the control box cover.
3. Route the electrical service from the subpanel
into the spa equipment compartment. Position
the conduit in the recess provided between the
frame and door. Install the supply conduit so as
not to block the drain valve.
4. NOTE: The subpanel must be placed in sight of
the spa, at a minimum distance of five feet away.
5. Connect the supply conduit to the bottom of the
IQ 2000
Spa Control Box, using a minimum of
3/4" liquid-tight, flex conduit fittings.
WIRING CONNECTIONS
1. Identify the TB-1 terminal block, located inside
the IQ 2000
control box at the lower left-hand
corner.
2. Connect the #12 AWG, Blue wire, from the
subpanel 20 amp breaker, terminal L1 to TB-1,
terminal 3.
3. Connect the #12 AWG, Red wire, from the
subpanel 20 amp breaker, terminal L2 to TB-1,
terminal 5.