ELECTRICAL INFORMATION
230V, 50 Amp,
2-POLE,
CIRCUIT BREAKER
(NON GFCI)
MAIN SERVICE
ELECTRICAL
PANEL
** Refer to NEC 250-122 (table)
NOTE: The wire connections to GFCI breakers are for reference only. Always ensure the white neutral wire is connected to the load neutral of the 20 amp breaker.
*PROVIDED WITH HOT TUB.

230 VOLT CONVERTED PRISM

The PRISM will run with a 50 service but requires an additional 20 amp
breaker in order to operate the heater and jet pump 3 at the same time.
Without the additional 20 amp breaker, the heater will NOT operate while
the jets are used with jet pump 3 on.
This subpanel requires a 70 amp, single phase, 230 volt, four wire
service (two line, one neutral, one ground). The ground wire must never
be less than #10 AWG. Use NEC 250-122 (table) and local codes for
more information. A minimum #6 AWG solid copper bond wire is also
required.
SOVEREIGN, PRODIGY, JETSETTER LX & BEAM II
230 volt permanently connected model
THE EXACT PHYSICAL LOCATION OF THE TERMINALS ON THE GFCI BREAKER
WILL VARY BETWEEN MANUFACTURERS. CONNECTING THE HOT WIRE TO THE
NEUTRAL TERMINAL WILL CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL BOX.
# 8 AWG WHITE, NEUTRAL
# 10 AWG GREEN, GROUND**
# 8 AWG BLUE, L1
# 8 AWG RED, L2
IMPORTANT!
FACTORY
WIRED
HEATER
L1 # 12 AWG BLUE
L2 # 12 AWG RED
N # 12 AWG WHITE
L1 # 10 AWG BLUE
L2 # 10 AWG RED
GROUND # 10 AWG GREEN
*SUBPANEL
Minimum 5 FEET
The Subpanel must be
WITH GFCI
within sight of the spa
Do not exceed 50 FEET.
BREAKERS
IMPORTANT: ALL WIRING SHOULD BE COPPER.
Mount the subpanel in the vicinity of the spa, but not within five feet, in
accordance with local codes.
HOT SPRING SPAS MUST BE WIRED IN ACCORDANCE WITH
ALL APPLICABLE LOCAL ELECTRICAL CODES. ALL ELECTRICAL
WORK SHOULD BE DONE BY AN EXPERIENCED LICENSED
ELECTRICIAN. WE RECOMMEND THE USE OF APPROPRIATE
ELECTRICAL CONDUIT, FITTINGS, AND WIRE FOR ALL CIRCUITS.
IMPORTANT: Service Technician must reconfigure spa using the soft
jumpers to allow spa heater to run concurrent with jet pump.
NOTE: Long wiring runs may require larger-gauge wire than stated.
GRD
System Ground Terminal
Remove power
jumpers A from TB-1