Component Specifications
MAIN FUSE
The main fuse is 250 Volt, 10 amp.
ICE/OFF/CLEAN TOGGLE SWITCH
Single-pole, double-throw switch. The switch is
connected into a varying low D.C. voltage circuit.
FAN CYCLE CONTROL
(Self-Contained Air-Cooled Models Only)
Model
QF800/QC700
HIGH PRESSURE CUTOUT (HPCO) CONTROL
Cut-Out
450 psig ±10
(3103 kPa ±69)
31 bar ±.69
TORQUE VALUES
Location
M24 Coupling
Evap to Foundation
Part Number 80-1230-9 10/10
Cut-In (Close)
250 ±5
(1723 kPa ±.34)
(17.23 bar ±.34)
(Must be below 300 psig
(2068 kPa 20.68 bar) to reset.)
Inch Pounds
Use Loctite 242
Automatic Reset
5-20
60 +/- 5
Cut-Out (Open)
200 ±5
(1517 kPa ±.34)
(15.17 bar ±.34)
Cut-In
Set Screws
#10-24
#1/4-20
229