3.Ultraviolet Lights; 4.Ventilator; Utility Curtailment - Carrier Infinity SYSTXCCITW01 Installation Instructions Manual

Infinity touch control
Hide thumbs Also See for Infinity SYSTXCCITW01:
Table of Contents

Advertisement

Change Pad: Selectable from 1 to 24 months
S
Default = 12 months
d
Humidify with Fan: Yes or No
S
Default = No
d
6.3.7.3.
Ultraviolet Lights
With this option, the installer has the option of selecting whether ultraviolet lights
are installed, and the time interval for changing the ultraviolet lights. After the
selections are made, touch SAVE.
UV Lights Installed: Yes or No
S
UV Lights selection made during installation; otherwise default = no
d
Change Interval: Selectable from 1 to 48 months
S
Default = 12 months
d
6.3.7.4.
Ventilator
When a ventilator is installed, the installer has the option of selecting the time
interval for cleaning the ventilator. After the selections are made, touch SAVE.
Clean Interval: Selectable from 60, 90, 120, 150 or 180 days
S
Default = 90 days
d
6.3.8.

Utility Curtailment

Utility Saver is used to force the equipment to a lower stage (low or off) when
activated by the utility company, typically during peak load times. This setup is
available only if the equipment has a utility saver input (refer to outdoor equipment
Installation Instructions). This setup controls the response of the equipment when
the utility saver input is active. DISABLED means that the curtailment function is
not active. TURN OFF means the outdoor unit is to be turned off when the
curtailment function is active. LOW STAGE means the outdoor unit will run in
42