switching reversing valve. This setup is only available on communicating heat
pumps. After the selection is made, touch SAVE.
Defrost Fan Delay: Yes or No
S
Default = No
d
6.3.4.7.
Brownout Disable
This option turns off the high voltage brownout detection function in the outdoor
unit control. After the selection is made, touch SAVE.
Brownout Disable: On or Off
S
Default = Off
d
6.3.4.8.
Energy Efficiency
This option is used to input the published ratings of the installed air conditioner or
heat pump as part of the energy tracking calculation. After the ratings are entered,
touch SAVE.
6.3.5.
Heat Source Lockout
First touch SETUP, then touch HEAT SOURCE LOCKOUTS to set up the
parameters for the AC/Heat Pump unit.
For hydronic heat applications, this option allows the installer to set the lockout
temperatures below the which only the hydronic coil will operate, and the lockout
temperature above which the hydronic coil will not operate. After the selections are
made, touch SAVE.
37