Automatic Fire Detectors LSN
improved
4

Programming

Programming occurs via a PC or laptop connected to the fire panel
420 series detectors are programmed by entering the area of operation. The selection of the
area of operation determines the optimum characteristic field for fire and disturbance variable
evaluation.
When optical sensor sensitivity in the FAP‑OTC 420 and FAP‑DOTC420 is low, the detector
only triggers if both smoke and an increase in CO concentration or temperature is detected.
The operating mode can be changed for the FAP‑OTC 420 and FAP‑OT 420 detector models,
as well as the FAP‑DOTC420 and FAP‑DOT420 models, i.e. individual sensors can be switched
off:
In the case of the purely optical FAP‑O 420 and FAP‑DO420 detectors, the sensitivity of the
optical sensor can be set to three levels. Depending on the operating location, the optical
sensor in the detector is thus adjusted to the environmental conditions.
Notice!
For fire detection, the purely optical detector also evaluates the time behavior of the fire char-
acteristics, which differs significantly from the time behavior of disturbance variables and that
i
occurring during a detector test
As a result, there are also different trigger times when testing with a test aerosol outside of
Walk test operation (10 s to max 60 s), depending on the selected sensitivity adjustment.
The FAH-T 420 Heat Detector is programmed by taking into account the ambient temperature,
the installation height and the sensitivity class selection.
Programming of the optical, thermal, and chemical sensors and the linking of all sensors via
algorithms significantly increases the detection ability and security against false alarms.
4.1
FAP‑DOTC420 / FAP-OTC 420
Notice!
The default setting of the FAP-DOTC 420 and FAP-OTC 420 detector types in RPS and Win-
i
Para is "Office (smoker) / Waiting Room / Restaurant /Meeting Room". For a description of
this setting, see the below table.
Selectable installation locations in
the programming software (WinPara
and FSP‑5000‑RPS)
Office (after hours)
Office (smoker)/waiting room/
restaurant/meeting room
= default setting
Office (day mode)
Bosch Sicherheitssysteme GmbH
With FSP‑5000‑RPS (Remote Programming System) for panels with LSN improved version
line technology
With WinPara version 4.85 for panels with conventional LSN line technology.
Switch to optical (O sensor sensitivity = low, T sensor = switched off)
Switch to thermal differential (T sensor sensitivity = A2R, O sensor = switched off)
Switch to thermal maximum (T sensor sensitivity = A2S, O sensor = switched off).
Detector Type
O, T
, T
max
diff
O, T
, T
max
diff
O, T
, T
max
diff
Sensitivity
Thermom
Optical
ax (T
)
(O)
max
, C
High (A2)
High
, C
High (A2)
Low*
, C
Low (B)
Medium
Operation Guide
Programming | en
Chemical
(C)
High
Low
High
12/2012 | 8.1 | F.01U.003.448