Automatic Fire Detectors LSN
improved
Connecting: Insert the stripped cable end (no braided wire) into the terminal.
Disconnecting: Turn wire alternately to the left and right, thus pulling it out of the terminal.
Up to 4 detectors can be connected to each MPA.
Three inputs (terminals 2-4) allow adjustment to various line technologies.
Connection depending on the line technology
Line technology
Conventional
Conventional
LSN
Terminal
1
2
3
4
A resistor is necessary to connect to terminal 4; otherwise, the LED
may be damaged.
All current Bosch detectors are equipped with an internal resistor to
restrict current consumption.
Caution!
If the current consumption for the connected detector exceeds 20 mA, it can lead to the mal-
!
function of or damage to the MPA.
You should restrict the maximum detector current consumption to 20 mA to avoid damaging
the MPA.
Notice!
i
The cable length between the detector and the MPA must not exceed 3 m when connected by
an unshielded cable.
MPA technical specifications
Operating voltage
Maximum current consumption
Display medium
Permissible wire gauge
Dimensions
Bosch Sicherheitssysteme GmbH
Fire panel
BZ 1060
FPA-5000, UEZ 1000, UGM 2020, FP 102/104/106
FPA-5000, FPA‑1200, BZ 500 LSN, UEZ 1000,
UEZ 2000 LSN, UGM 2020
Connection
Ground
Entry point flashing (LED flashes)
Entry point static (LED flashes)
Entry point static (LED flashes)
Terminal 2
Terminal 3
Terminal 4
9 V DC to 30 V DC
approx. 2 mA
limited to approximately 13 mA
limit to maximum 20 mA
1 LED
0.6 mm. . . 0.8 mm
79 x 79 x 31 mm
Operation Guide
Accessories | en
29
Terminals
1 + 2
1 + 3
1 + 4
1 2 3 4
12/2012 | 8.1 | F.01U.003.448