Fah-T 420/Fah-T 420-Kkw - Bosch FAP-DO420 Operation Manual

Automatic fire detectors lsn improved
Hide thumbs Also See for FAP-DO420:
Table of Contents

Advertisement

14
en | Programming
Installation locations
Theater/concert hall
Warehouse with vehicle traffic
Office (smoker)/waiting room/restaurant/meeting room
Conference hall/waiting room/fairground
Office (after hours)
School/kindergarten
Production location
EDP room
High storage warehouse without vehicle traffic with combustion
engine
Office (day mode)
4.4

FAH-T 420/FAH-T 420-KKW

Selectable installation locations in the programming software (WinPara and
FSP‑5000‑RPS)
§ A2R
A2S
A1R
A1
BR
BS
§ = Basic setting in the WinPara and FSP‑5000‑RPS programming software
Sensitivity classes as per EN 54 Part 5
With the detector types FAH‑T 420 and FAH‑T 420‑KKW, it is possible to set one of the
sensitivity classes listed above in line with planning.
In the sensitivity classes A1, A2S and BS, the FAH-T 420 or FAH‑T 420‑KKW is operated purely
as a thermal maximum detector. In this case, the detector does not activate at below 54 °C in
class A2S, and not below 69 °C in class BS.
The sensitivity classes A2S and BS are therefore particularly suitable for applications where
higher temperature rates-of-rise occur over a longer period, e.g. in kitchens or boiler rooms.
The sensitivity classes A1R, A2R and BR indicate that the thermal differential unit is active in
addition to the thermal maximum unit.
These sensitivity classes are especially well-suited for use in unheated buildings where the
ambient temperature can vary greatly but high temperature rates-of-rise do not last long.
The thermal differential unit enables class A1R/A2R detectors to respond at T<54 °C and class
BR detectors at T<69 °C.
The selection of the sensitivity class also depends on the installation height of the detector.
12/2012 | 8.1 | F.01U.003.448
Typical application temperature: 25 °C, T
Typical application temperature: 25 °C, only T
Typical application temperature: 25 °C, T
Typical application temperature: 25 °C, only T
Typical application temperature: 40 °C, T
Typical application temperature: 40 °C, only T
Operation Guide
Automatic Fire Detectors LSN
Selectable sensitivity
Medium
Low
Low
Low
High
Medium
Low
High
High
Medium
+ T
, height up to 6 m
max
diff
, height up to 6 m
max
+ T
, height 6 m to 7.5 m
max
diff
, height 6 m to 7.5 m
max
+ T
, height up to 6 m
max
diff
, height up to 6 m
max
Bosch Sicherheitssysteme GmbH
improved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fap-420Fah-420

Table of Contents