en | Programming
4

Programming

Programming occurs via a PC or laptop connected to the fire panel with FSP-5000-RPS
(Remote Programming System) for panels with LSN improved version line technology
The FAP-425/FAH-425 series detectors are programmed by entering the area of operation. The
selection of the area of operation determines the optimum characteristic field for fire and
disturbance variable evaluation.
When optical sensor sensitivity in the FAP-425-DOTC-R is low, the detector only triggers if
both smoke and an increase in CO concentration or temperature is detected.
The operating mode can be changed for the FAP-425-OT-R/FAP-425-OT detector models, as
well as the FAP-425-DOTC-R and FAP-425-DOT-R models, i.e. individual sensors can be
switched off:
In the case of the purely optical FAP-425-O-R/FAP-425-O and FAP-425-DO-R detectors, the
sensitivity of the optical sensor can be set to three levels. Depending on the operating
location, the optical sensor in the detector is thus adjusted to the environmental conditions.
Notice!
For fire detection, the purely optical detector also evaluates the time behavior of the fire
characteristics, which differs significantly from the time behavior of disturbance variables and
that occurring during a detector test
As a result, there are also different trigger times when testing with a test aerosol outside of
Walk test operation (10 s to max 60 s), depending on the selected sensitivity adjustment.
The FAH-425-T-R is programmed by taking into account the ambient temperature, the
installation height and the sensitivity class selection.
Programming of the optical, thermal, and chemical sensors and the linking of all sensors via
algorithms significantly increases the detection ability and security against false alarms.
4.1

FAP-425-DOTC-R

Notice!
The default setting of the FAP-425-DOTC-R detector in RPS is "Office (smoker) / Waiting
Room / Restaurant /Meeting Room". For a description of this setting, see the below table.
Selectable installation locations in
the programming software
(FSP‑5000‑RPS)
Office (after hours)
Office (smoker)/waiting room/
restaurant/meeting room
= default setting
Office (day mode)
EDP room
2014.11 | 1.1 | F.01U.283.550
Switch to optical (O sensor sensitivity = low, T sensor = switched off)
Switch to thermal differential (T sensor sensitivity = A2R, O sensor = switched off)
Switch to thermal maximum (T sensor sensitivity = A2S, O sensor = switched off).
Detector Type
O, T
, T
max
diff
O, T
, T
max
diff
O, T
, T
max
diff
O, T
, T
max
diff
Sensitivity
Thermom
Optical
ax (T
)
(O)
max
, C
High (A2)
High
, C
High (A2)
Low*
, C
Low (B)
Medium
, C
High (A2)
High
Operation Guide
AVENAR detector 4000
Chemical
(C)
High
Low
High
High
Bosch Sicherheitssysteme GmbH