38
en | Maintenance and Service
8.1

Notes for the Service

Notice!
With the exception of the special KKW detector types, you can use the WinPara programming
i
software (V 4.53 or higher) to display the serial number, contamination level, operating hours
and current analog values for all configured detectors.
8.1.1

Display of Operating Data in WinPara

Module Address
Module where the detector or detector line is installed.
Address
Detector installation address, e.g. 10-03: The detector is in zone 10 and is the detector
number 3.
Brief Info
Additional information entered during programming. e.g. "FAP-O 420 on MSS400" means that
the FAP-O 420 is installed together with an MSS 400 Detector Base Sounder. You can also
enter the position of the detector here.
Type
display of the set detector type.
Serial number
The first digit of the 8-digit serial number represents the year of manufacture, i.e. a detector
with the serial number 3931859 was manufactured in 2003.
Current analog values
Optical system value (display of the current contamination value):
0 . . . 170
12/2012 | 8.1 | F.01U.003.448
Every detector base has a Chamber Maid Plug
(cleaning opening with a plug) for blowing out
the optical chamber with compressed air (not
required for the FAH‑T 420 Heat Detector).
Initial set-up value for a new detector
Operation Guide
Automatic Fire Detectors LSN