Electrical Data - Carrier SYNERGY 2000 38YDA Product Data

Two-speed electric heat pump
Table of Contents

Advertisement

Electrical data

UNIT SIZE-
SERIES
V/PH
036-30
048-30
208/230/1
060-30
* Permissible limits of the voltage range at which unit will operate
satisfactorily.
† Time-delay fuse.
‡ Length shown is as measured 1 way along wire path between unit and
service panel for voltage drop not to exceed 2%.
** If wire is applied at ambient greater than 30 ° C (86 ° F), consult Table
310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name
ROMEX, shall be that of 60 ° C (140 ° F) conductors, per the NEC
(ANSI/NFPA 70) Article 336-30.
If other than uncoated (non-plated), 60 or 75 ° C (140 or 167 ° F) insula-
tion, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used, consult applicable tables of the NEC
(ANSI/NFPA 70).
4
OPER VOLTS*
COMPRESSOR
Max
Min
LRA
90.0
253
187
120.0
141.0
FAN
RLA
FLA
MCA
17.6
1.5
23.5
23.6
1.5
31.0
30.8
1.5
40.0
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, Refrigeration
LRA
— Locked Rotor Arms
MCA
— Minimum Circuit Amps
RLA
— Rated Load Amps
NOTE: Control circuit is 24v on all units and requires external power
source 27va minimum. Copper wire must be used from service
disconnect to unit. All motors/compressors contain internal overload
protection.
MAX FUSE†
MAX
MIN WIRE
LENGTH
HACR TYPE
SIZE
(Ft)‡
CKT BKR
60 ° C/75 ° C**
60 ° C/75 ° C**
AMPS
12/12
52/50
8/10
100/61
8/8
78/74
OR
40
50
60