Combination ratings continued
UNIT
SIZE-
INDOOR
SERIES
MODEL
CC5A/CD5A/CD5BA060
CC5A/CD5A/CD5BW060
CD3(A,B)A060
060-30
CD3CA060
CE3AA060
CJ5A/CK5A/CK5BA060
CJ5A/CK5A/CK5BX060
CK3BA060
* Tested combination.
† Capacities shown are at ARI rating point 47 ° F, high speed. Unit is factory shipped to operate on low speed at 47 ° F. See Heat Pump Heating Per-
formance tables for low speed capacity at 47 ° F.
NOTES:
1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.
2. Rating values reflect coil combinations plus field-installed TXV (except when specifying FK4 and FC4 coils).
3. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for heat pumps. Ratings for other
combinations are determined under DOE computer simulation procedures.
4. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.
5. Do not apply to capillary tube coils.
6. Unit is factory set to change speeds in heating mode based on ambient temperature. See Ambient Temperatures for High- and
Low-Speed Operation table for speed change temperatures.
7. Coefficient of Performance (COP) can be calculated by using the Heat Pump Heating Performance tables. Normally the high tempera-
ture COP is calculated at 47 ° F, and the low temperature COP is calculated at 17 ° F. The formula for calculating the COP is as follows:
THC
COP =
KW x 3.413
THC=total heating capacity at either 47 ° F or 17 ° F, 70 ° F indoor dry bulb and rated airflow.
KW=power input in kilowatts.
10
EVAP AIR CFM
COOLING CAPACITY
High
Low
High
COILS + 58U(H,X)V120-20 VARIABLE-SPEED FURNACE
1840
1135
53,000
1825
1135
55,000
1840
1156
53,000
1795
1130
53,000
1840
1135
55,000
1830
1135
54,000
1835
1135
55,000
1830
1135
54,000
AMBIENT TEMPERATURES FOR HIGH- AND
LOW-SPEED OPERATION
AMBIENT TEMPERATURE ( ° F)
UNIT
SIZE
High Speed
036
30 or less
048
33 or less
060
40 or less
HEATING CAPACITY
SEASONAL
Low
EFF (SEER)
High†
30,000
13.00
53,000
30,600
13.30
54,000
30,000
13.00
53,000
30,000
13.00
54,000
30,600
13.30
54,000
30,600
13.00
54,500
31,200
13.50
55,000
30,600
13.00
54,500
Low Speed
31 or greater
34 or greater
41 or greater
SOUND
RATING
SEASONAL
High/Low
Low
EFF (HSPF)
(dBA)
29,000
7.80
80/72
29,200
8.00
80/72
29,000
7.80
80/72
29,200
8.00
80/72
29,200
8.00
80/72
30,400
7.80
80/72
30,400
8.00
80/72
30,400
7.80
80/72

Hide quick links: