Physical And Electrical Data; Physical Data, Units Without Options 150 And 6 - Carrier AQUAFORCE 30XW Series Installation, Operation And Maintenance Instructions

Water-cooled screw chillers, water-sourced screw heat pumps
Hide thumbs Also See for AQUAFORCE 30XW Series:
Table of Contents

Advertisement

4 - PHYSICAL AND ELECTRICAL DATA

4.1 - Physical data, units without options 150 and 6

■ Standard-efficiency units
30XW--/30XWH
Sound levels - standard unit
Sound power level
(1)
Sound pressure level at 1 m
(2)
Sound levels - standard unit + option 257
Sound power level
(1)
Sound pressure level at 1 m
(2)
Dimensions - standard unit
Length
Width
Height
Operating weight
(4)
Compressors
Circuit A
Circuit B
Refrigerant
(4)
Circuit A
Circuit B
Oil - standard unit
Circuit A
Circuit B
Capacity control
Minimum capacity
(5)
Evaporator
Net water volume
Water connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
Condenser
Net water volume
Water connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
(1) In dB ref=10
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in
-12
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information,
calculated from the sound power level Lw(A).
(3) Option 257 = Low noise level.
(4) Weight shown is guideline only. Please refer to the unit nameplate.
(5) Minimum unit capacity corresponds to a physical state of the unit and is given for indication only. The actual capacity at this stage depends on operating conditions.
dB(A)
dB(A)
(3)
dB(A)
dB(A)
mm
mm
mm
kg
kg
teqCO
2
kg
teqCO
2
l
l
%
l
in
in
kPa
l
in
in
kPa
Eurovent certified values
254
304
354
402
95
95
95
99
78
78
78
82
-
-
-
96
-
-
-
78
2724
2724
2724
2741
928
928
928
936
1567
1567
1567
1692
2017
2036
2072
2575
Semi-hermetic 06T screw compressors, 50 r/s
1
1
1
1
-
-
-
-
84
80
78
92
120
114
112
132
-
-
-
-
-
-
-
-
23,5
23,5
23,5
32
-
-
-
-
SmartVu
, electronic expansion valves (EXV)
TM
15
15
30
30
Multi-pipe flooded type
50
56
61
70
5
5
5
5
3/8
3/8
3/8
3/8
1000
1000
1000
1000
Multi-pipe flooded type
55
55
55
76
5
5
5
5
3/8
3/8
3/8
3/8
1000
1000
1000
1000
452
552
602
652
99
99
99
99
82
82
82
82
96
96
96
96
78
78
78
78
2741
2741
2741
3059
936
936
936
1040
1692
1692
1692
1848
2575
2613
2644
3247
1
1
1
1
-
-
-
-
R-134a
92
92
92
145
132
132
132
207
-
-
-
-
-
-
-
-
32
32
32
36
-
-
-
-
30
30
30
15
70
70
70
109
5
5
5
6
3/8
3/8
3/8
3/8
1000
1000
1000
1000
76
76
76
109
5
5
5
6
3/8
3/8
3/8
3/8
1000
1000
1000
1000
702
802
99
99
82
82
96
96
78
78
3059
3059
1040
1040
1848
1848
3266
3282
1
1
-
-
135
125
193
179
-
-
-
-
36
36
-
-
15
30
109
109
6
6
3/8
3/8
1000
1000
109
109
6
6
3/8
3/8
1000
1000
13

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AQUAFORCE 30XW Series and is the answer not in the manual?

Table of Contents