Physical And Electrical Data - Carrier 38AJ 008 Installation, Operation And Maintenance Instructions

Air-cooled condensing units
Table of Contents

Advertisement

38AJ/AZ
Nominal cooling capacity 38AJ*
Nominal cooling capacity 38AZ* kW
Operating weight**
Refrigerant
38AJ
38AZ
Compressor
Number of compressors
Number of capacity steps
Minimum capacity
Outdoor coil
Fan
Quantity
Total air flow
Speed
Pipe connection diameter
Suction line
Liquid line
Legend:
*
Nominal capacities are based on:
- a saturated suction temperature (R-22) or a suction dew point temperature (R-407C) of 7.2°C
- an outdoor air temperature (OAT) of 35°C
** Unit weight without options
38AJ/AZ
Power supply
Nominal power supply
Voltage range
Auxiliary circuit
Auxiliary circuit power input
(heaters)
Fan power input
Fan power supply
Nominal unit power input*
Maximum unit power input**
400 V-3 ph-50 Hz (360 V-440 V)
Maximum starting current (ICF)
Nominal unit current drawn*
Maximum unit current drawn**
230 V-3 ph-50 Hz (207 V-253 V)
Maximum starting current (ICF)
Nominal unit current drawn*
Maximum unit current drawn**
Legend:
*
Saturated suction temperature (R-22) or a suction dew point temperature (R-407C) of 7.2°C, outdoor air temperature (OAT) of 35°C
** Maximum unit operating conditions (saturated suction temperature (R-22) or a suction dew point temperature (R-407C) of 10°C, saturated discharge temperature (R-
22) or discharge dew point temperature of 68.3°C.
*** ICF = maximum instantaneous current during starting, equal to the current value of the last compressor to start, plus the sum of the maximum currents of the other
compressors and fans ooperating.
Electrical data notes:
The units have a single power connection point.
A separate power source (230 V, 1 ph, 50 Hz) that does not exceed the main switch
capacity is required to power the compressor crankcase heater circuit. This source
must be supplied from a transformer. It must not be supplied from a phase + neutral
supply (for ground + neutral systems).
The control box includes the following standard features:
-
Starter and motor protection devices for each compressor and the fan(s)
-
Control devices
Field connections:
All connections to the system and the electrical installations must be in full
accordance with all applicable local codes.
These Carrier units are designed and built to ensure conformance with local codes.
The recommendations of European standard EN 60 204-1 (machine safety - electrical
machine components - part 1: general regulations) are specifically taken into account,
when designing the electrical equipment.
NOTES:
Conformance with EN 60 204 is the best means of ensuring compliance with the
Machines Directive § 1.5.1. Generally the recommendations of IEC 364 are accepted
as compliance with the requirements of the installation directives.
Annex B of EN 60204-1 describes the electrical characteristics used for the operation of
the machines.
6
008
010
012
kW
23.3
29.4
36.5
21.5
27.5
34.2
kg
248
250
264
R-22
R-407C
Hermetic
1
1
1
1
1
1
%
100
100
100
Copper tubes and aluminium fins
Direct drive, propeller
1
1
1
l/s
2640
2640
2640
r/s
15
15
15
in
1-1/8
1-1/8
1-1/8
5/8
5/8
5/8
008
010
012
V-ph-Hz 400-3-50
V
360-440
V-ph-Hz 230-1-50
W
70
70
70
kW
0.70
0.70
0.70
400-3-50
kW
7.5
10.4
14.5
kW
8.6
13.0
16.1
A
81
110
135
A
12.9
17.8
24.9
A
24.5
31.0
38.5
A
140
190
233
A
22.3
30.9
43.2
A
42.4
54.0
67.0
Physical data
014
018
024
51.0
61.0
76.0
47.3
57.0
69.0
376
431
477
Semi-hermetic
1
1
1
2
2
2
66
50
66
Shrouded axial, Flying Bird low-noise fan
1
1
1
4700
4700
4700
12.5
12.5
12.5
1-3/8
1-5/8
1-5/8
5/8
5/8
7/8
Electrical data
014
018
024
100
200
200
1.14
1.14
1.14
13.5
18.3
25.9
18.6
22.3
29.2
84
104
134
23.2
31.5
44.5
34.0
38.9
51.0
146
180
232
40.2
55.0
77.0
59.0
67.0
88.0
1. The operating environment for these units is specified below:
Environment* - Environment as classified in EN 60 721:
-
outdoor installation*
-
ambient temperature range: -25°C to +46°C, class 4K4H*
-
altitude: < 2000 m*
-
presence of hard solids, class 4S2 (no significant dust present)
-
presence of corrosive and polluting substances, class 4C2 (negligible)
-
vibration and shock, class 4M2
Competence of personnel, class BA4* (trained personnel - IEC 364)
2. Power supply frequency variation: ± 2 Hz.
3. The neutral (N) line must not be connected directly to the unit (if necessary use a
transformer).
4. Overcurrent protection of the power supply conductors is not provided with the unit.
5. The optional factory-installed circuit breaker is of type "a" (EN 60 204-1 § 5.3.2).
NOTE: If particular aspects of an actual installation do not conform to the conditions
described above, or if there are other conditions which should be considered, always
contact your local Carrier representative.
* The required protection level for this class is IP43BW (according to reference
document IEC 529). All units are protected to IP44CW and fulfill this protection
condition.
030
036
046
062
93.0
119.0
139.0
170.0
85.0
113.0
129.0
158.0
644
682
1185
1422
1
1
2
2
2
2
4
4
66
66
33
33
2
2
2
4
9400
9400
9400
18800
12.5
12.5
12.5
12.5
1-5/8
2-1/8
1-5/8
2-1/8
7/8
7/8
7/8
7/8
030
036
046
062
200
200
400
400
2.30
2.30
2.30
4.60
27.0
39.4
51.0
55.0
34.9
47.3
59.0
70.0
152
207
194
219
46.4
68.0
88.0
95.0
60.0
83.0
102.0
120.0
263
359
336
379
80.0
117.0
152.0
165.0
104.0
144.0
177.0
208.0
074
233.0
219.0
1492
2
4
33
4
18800
12.5
2-1/8
7/8
074
400
4.60
77.0
95.0
296
133.0
166.0
512
230.0
288.0