5
Commissioning
5.1
Mechanical Set-Up
Note the following points when setting up the UPS system
and its external battery units (special accessories):
Make sure the rack is able to support the weight. This is
particularly important in conjunction with external battery
units (special accessories).
Install the units so that adequate air circulation is
assured. There must be at least 100 mm clearance at the
back for ventilation purposes. Do not block the intake
openings on the front and, if present, on the side of the
unit. There must be a gap of at least 50 mm here.
Avoid extreme temperatures! We recommend an ambient
temperature of 15 °C to 25 °C in order to maximise the
service life of the batteries. Do not expose the units to
direct sunlight or operate them close to other heat
sources such as radiators.
Protect the units against external effects (in particular
moisture and dust). In this regard, please also refer to the
instructions in chapter 4.2, page 9 in these operating
instructions.
If you transport the unit from a cold room into a warm one, or
if the room temperature suddenly drops then condensation
may form inside the unit. To avoid any damage due to
condensation, leave the unit to acclimatise for 2 hours before
you switch it on.
5.1.1
Set-Up in a 19 " Rack
PROTECT C. 1000 R (S), C. 2000 R (S), C. 3000 R (S) and
C. 6000 R are to be installed in a 19"- Rack. Mount the units
preferable in the lower third of your rack considering the
centre of gravity of the rack and an adequate air circulation.
You will receive adequate rack rails at your specialist dealer.
27