provided mains connection cable to a customary shockproof
socket. Make sure that the dimension of the circuit breaker is
sufficient. Especially the PROTECT C. 3000 R (S) needs a
circuit breaker with 16A.
The PROTECT C. 6000 R is connected directly with the
modules via the terminal block. The cable diameter of each
conductor is 6 mm². The circuit breaker has to have the
dimension of 32 A.
After connecting the unit to the mains, connect the outputs of
your UPS to your loads. Use the load connection cables
provided for this. Don't switch on the loads yet. Please
contact your dealer if you require additional load connection
cables.
If you are using combined rack (circuit with
mains and UPS-power) mark each circuit with
the corresponding supply (mains or UPS).
The output of PROTECT C. 6000 R should supply additional
separated circuits. Make sure that circuit protection is set up
selectively.
The
PROTECT C. 6000 R and the sub distribution must have a
diameter of 6 mm². Please note the following information in
the sub distribution.
 Maximal allowed total load
 Maximal allowed load for each loads output
2.
Activate the mains input circuit breaker. If
necessary switch it to "ON".
Default setting for PROTECT C. 1000 R (S),
i
C. 2000 R (S) and C. 3000 R (S): No automatic supply
for load over integrated bypass after executing
step 1 and 2 (Modification of the configuration
with the provided Software "CompuWatch").
Default setting for C. 6000 R: Automatic supply for
i
load over integrated bypass after executing step 1
and 2 (Modification of the configuration with the
provided Software "CompuWatch").
3.
Now switch on the UPS. To do this, press and hold
the UPS ON switch for about 2 seconds.