PENSOTTI PCH 18 Instruction Manual page 35

Wall mounted heat only boiler premix condensing system boiler
Table of Contents

Advertisement

P
ARAMETER
01
Not applicable
110V 60Hz
S
P 1 3
110V 60Hz
S
P
ARAMETER
02
6. Use buttons „+‟ o „-‟ to modify the value of the parameter:
110V 60Hz
S
00 = boiler with atmospheric burner;
01 = boiler with premix burner 25 kW;
02 = boiler with premix burner 34 kW ;
03 = boiler with premix burner 50 kW ;
7. Press and release button „S‟ to confirm. The parameter number
P 1 4
(14) will appear on the display.
110V 60Hz
S
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
P
ARAMETER
00
6. If the system is fitted with zone valves, set the parameter at „01‟. If
110V 60Hz
S
a remote control is installed, an extra interface board must be
installed to control the zone valves. Then set the parameter at „01‟.
7. Press and release button „S‟ to confirm. The parameter number
(15) will appear on the display.
P 1 5
8. Switch off the appliance and switch it back on again to render the
110V 60Hz
new parameter operative.
S
P
ARAMETER
00
6. If a telephone interface is installed, enable the board by setting
110V 60Hz
parameter 16 at „01‟;
S
7. Press and release button „S‟ to confirm. The parameter number
(16) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
P 1 6
N.B.: The connection of the telephone interface to contact TA of the
110V 60Hz
terminal board must be wired in parallel with the remote control using
S
two non-polarised conductors.
REGULATION INSTRUCTIONS
13 – D.H.W
PRIORITY
14 – T
YPE OF BURNER
15 – Z
ONED SYSTEM
16 – T
ELEPHONE CONTROL
31