4.2 Filling the system
Use only clean tap water to fill the system.
Once the water pipes have been connected, close the
gas feed valve and fill the system as follows:
Check that the circulation pump runs freely;
Check that the plug of the air vent valve has been
slackened slightly to allow air to escape from the
system (fig.1);
Open the filling tap R (fig. 2);
Unscrew the plug on the pump to remove any
trapped air, check that the pump is free then re-
tighten it when water starts to flow out;
Open the air vents on the radiators and monitor
the air evacuation process. When water starts to
flow out of the radiators, close the air vents;
Use the pressure gauge M (fig. 2) to check that
the system pressure reaches 1 bar and that the
code H2O does NOT appear on the control panel
display (see 2.7 section „Control Panel‟);
If, after the above operations, there is a reduction
in the pressure, re-open the filling tap R until the
pressure gauge reads 1 bar and that the code
H2O disappears on the control panel display;
On completion, make sure that the filling tap R
is perfectly closed.
Emptying the central heating system
Whenever it is necessary to empty the system,
proceed as follows:
turn off the main power supply switch;
wait for the boiler to cool down;
turn the system drain tap RS (see fig. 2) and use a container to collect the water that runs out;
INSTALLATION INSTRUCTIONS
Fig. 1
Fig. 2
23
AIR VENT VALVE
AIR VENT VALVE PLUG
PUMP
PUMP PLUG
R M