Table 2-7 Advanced Settings Fields - HVAC Field Descriptions (Continued)
Field
Auxiliary Heat
Aux Heat Offset
Aux Heat Delay
Heat Control
Cool Control
Internet Managed Thermostat Configuration Guide, Release 1.0
Part No. 600-03001-350, Rev. 1
Description
Specifies a secondary source of heat outside the heat pump
system, for example, electric baseboard or a gas furnace.
Note: In a dual stage heat pump, Auxilliary Heat is available
only after the 2nd stage is active.
Disabled – Disables Auxiliary Heat.
Enabled – Auxilliary Heat can be used while the heat pump
compressor is active.
Enabled without Compressor – Disables the compressor
when Auxiliary Heat is active.
Specifies the setting in degrees that the air temperature has to be
below the zone temperature to activate the Aux Heat source. The
default value is -2F, for example if the heat setpoint is 70F and
the air temperature drops below 68F the Aux Heat source will be
turned on. The range is from -6 to 0.
Specifies the delay between the active heat pump cycle and
activation of the Auxiliary Heat source.
Specifies the HVAC control of this thermostat. This parameter
describes the thermostat's capability to control a heat pump
system. The thermostat can also be disabled from controlling a
heating system and instead operate as a cool-only thermostat.
Disabled – Specifies that there is no heating system present.
(A/C only thermostat.)
1H – Enables the heat pump as a standard single stage
heating system.
Specifies the HVAC control of this thermostat. This parameter
describes the thermostat's capability to control a heat pump
system. The thermostat can also be disabled from controlling a
cooling system and instead operate as a heat-only thermostat.
Disable – Specifies that there is no cooling system present.
(Heat only thermostat.)
1C – Enables the heat pump as a standard single stage
cooling system.
Advanced Page
2-27