Iron Bleed-Through - Kinetico Commercial Plus Softener Series Owner's Manual

Commercial plus softener series
Table of Contents

Advertisement

CP Softener Series Owners Manual
Iron Bleed-through
Problem
Reason
Solution
1. Customer
[J
Previous iron buildup inside existing
Verify that customer plumbing
plumbing
plumbing after the water softener
is the problem by testing the
water quality at the brine
fitting with water running
2. The water meter
[J
The composition of raw water can change
Check the hardness and iron
disc is not set
with time
content of raw water. Install
properly for
the correct disc for current
cu rrent raw water
raw water conditions.
conditions
3. The salt setting is
[J
The composition of raw water can change
Check the hardness and iron
not set properly
with time
content of raw water. Set the
for current raw
brine valve for current raw
water conditions
water conditions
4. The iron may be
ferric iron
[J
Ferric iron is not removable by ion
exchange
Verify by using the demo
softener to determine if iron is
removable by ion exchange.
Add additional equipment if
needed
[J
The iron may be finer than the micron
rating of the installed prefilter cartridge
Install a cartridge with finer
micron rating
5. The customer's
[J
A galvanized pressure tank will create
Replace the galvanized
plumbing may
oxidized iron
pressure tank with a bladder
include a
style pressure tank
galvanized
pressure tank.
Pressure loss
Problem
Reason
Solution
1. Reduced pressure
entering the unit
[J
The prefilter is clogged
Replace the clogged prefilter
2. The upper and/or
[J
Foreign matter from the input lines is
Clean the distributors. Add a
lower distributors
accumulating in the distributors
prefilter to eliminate the
are plugged
foreign matter before it
enters the unit.
Rev. 08109
Kinetico Incorporated
+
Corporate Headquarters
+
Newbury, Ohio 44065
+
440-564-9111
Product No. 11160D
Page - 33