High Salt Consumption
Problem
Reason
Solution
1. Regenerates too
frequently.
CJ
See the section entitled Frequent
Regeneration
See the section entitled
Frequent Regeneration
2. Water level in the
CJ
The brine valve is set wrong or non-
Verify the brine valve setting.
brine drum is too
conforming
Replace non-conforming
high.
brine valve.
CJ
The brine valve or the brine drum is dirty
Clean brine valve and drum
CJ
The brine valve leaks
Tighten the connectors on
the brine valve
Salty Treated Water
Problem
Reason
Solution
1. Restricted drain
CJ
The drain is kinked or clogged
Clear any obstructions. Make
line
sure that the drain line flows
smoothly and unrestricted.
2. Low water
pressure
CJ
The unit should not see water pressure
drop below 15 psi on the outlet at any
time. During the backwash portion of the
regeneration cycle, it must hold at least
15 psi or the brine may not rinse out
completely.
Test the outlet pressure with
the unit in backwash and one
faucet at high flow. Measure
the pressure by placing a
gauge on the brine fitting.
Raise pressure if below 15
psi.
CJ
The prefilter cartridge is plugged
Replace prefilter cartridge
3. The backwash flow
CJ
Without enough backwash flow to the
Clean the backwash flow
control is plugged
drain, the unit cannot wash all the salt
control
from the media tanks
4. The drain is
CJ
Such drain runs can put back-pressure on
Locate a closer drain or use a
extremely long or
the unit and restrict the drain flow. This
larger diameter drain line
placed higher than
causes the same result as number 3
8 feet above the
above.
floor
5. The upper
CJ
Foreign material that finds its way into the
Clean upper distributors.
distributors are
media tanks may be collected around the
Install a prefilter
plugged. (This
upper distributors during backwash,
does not apply to
clogging them
High Efficiency
softeners)
6. Water level in the
CJ
The brine valve is set wrong or non­
Verify the brine valve setting.
brine drum is too
conforming
Replace non-conforming
high
brine valve