Available languages

Wire cover
Screw
Wire cover
Screw
Insert the wire cover tab into the square hole
of the indoor unit and fasten with a screw.
7.3. How to connect wiring to the
terminals
Caution when wiring cable
When stripping off the insulation of a lead wire, always
use a special tool such as a wire stripper. If there is no
special tool available, carefully strip the insulation with
a knife etc.
(1) Use crimp-type terminals with insulating sleeves as
shown in the ¿ gure below to connect to the terminal
block.
(2) Securely clamp the crimp-type terminals to the wires
using an appropriate tool so that the wires do not come
loose.
Strip : 10 mm (13/32 in.)
(3) Use the speci¿ ed wires, connect them securely, and
fasten them so that there is no stress placed on the
terminals.
(4) Use an appropriate screwdriver to tighten the terminal
screws. Do not use a screwdriver that is too small, oth-
erwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, other-
wise, the screws may break.
Screw with special washer
Crimp-type terminal
Wire
Terminal blocks
En-10
9332279030-04_IM.indb 10
9332279030-04_IM.indb 10
Cable clamp
Screw
Connection cable
Connection cable
Cable clamp
Screw
Connection cable
Crimp-type
terminal
Sleeve
Screw with special washer
Crimp-type
terminal
Wire
(6) See the table below for the terminal screw tightening
torques.
Tightening torque [N·m (lbf·in)]
M4 screw
CAUTION
• Match the terminal block numbers and connection cable
colors with those of the outdoor unit or branch box.
Erroneous wiring may cause burning of the electric parts.
• Connect the connection cables ¿ rmly to the terminal block.
Imperfect installation may cause a ¿ re.
• Always fasten the outside covering of the connection cable
with the cable clamp. (If the insulator is chafed, electric
discharge may occur.)
• Always connect the ground wire.
• Do not use the ground screw of the indoor unit for the
connection other than a speci¿ ed outdoor unit or branch
box.
1.2 to 1.8 (11 to 16)