8. DRAIN PIPING
• Install the drain pipe with downward gradient (1/50 to
1/100) and so there are no rises or traps in the pipe.
• Use general hard polyvinyl chloride pipe (VP25) [outside
diameter 1-1/2" (38 mm)].
• During installation of the drain pipe, be careful to avoid
applying pressure to the drain port of the indoor unit.
• When the pipe is long, install supporters. (Fig. 31 )
• Do not perform air bleeding.
• Always heat insulate (11/32" (8 mm) or over thick) the
indoor side of the drain pipe.
Fig. 31
Drain pipe
Arrange the drain pipe
lower than this position.
Lifted
up
BAD
Supporter
5 to 6.5 ft (1.5 to 2 m)
(1) Install insulation for the drain pipe. (See Figs. 32 and 33.)
Cut the included insulation material to an appropriate
size and adhere it to the pipe.
Fig. 32
Indoor unit
Drain pipe insulation
(drain port)
(accessories)
Fig. 33
Indoor unit
No gap
(2) If "
Right rear piping ": fasten the drain pipe with
VT wire so that the pipe slopes correctly within the
indoor unit. (Fig. 34)
Fig. 34
Indoor unit (rear view)
GOOD
Wave
BAD
End in water
Drain pipe
Insulation for Drain pipe
(To be obtained locally.
Length should be at least
11/32" (8 mm).)
Drain pipe insulation
Drain pipe
13/32" (10 mm)
or over
VT wire
Drain hose
9. ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire cut-
ting pliers, then strip the insulation to about
15/16" (25 mm) to expose the solid wire.
(2) Using a screwdriver, remove the terminal screw
(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the ter-
minal board and tighten securely with the termi-
nal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire cut-
ting pliers, then strip the insulation to about 3/8"
(10 mm) to expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw
(s) on the terminal board.
(3) Using a round terminal fastener or pliers, securely
clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and
tighten the terminal screw with a screwdriver.
Fig. 35
Solid wire
Insulation
Wire
Terminal block
9
Strand wire
Round terminal
Loop
Screw with
special washer
Screw with
special washer
Round
terminal
Terminal
Round
board
terminal
Wire
Need help?
Do you have a question about the SPLIT TYPE AIR CONDITIONER and is the answer not in the manual?