Extended Data 2 I/O Mapping; Operation Command And Inverter Status Registers - Omron 3G3AX-MX2-PRT-E User Manual

Mx2/rx profibus option board
Hide thumbs Also See for 3G3AX-MX2-PRT-E:
Table of Contents

Advertisement

Extended Data 2 I/O Mapping

C-3
Extended Data 2 I/O Mapping
C-4

Operation Command and Inverter Status Registers

Table C-4 Conventional control status regs
Bit
Operation Command
Name
0
Forward Run/Stop (FW) 1: Run forward
1
Reverse Run/Stop (RV) 1: Run reverse
2
Intelligent Input
Terminal override [3]
3
Intelligent Input
Terminal override [4]
4
Intelligent Input
Terminal override [5]
Intelligent Input
5
Terminal override [6]
Intelligent Input
6
Terminal override [7]
80
Note
The Torque Compensation only becomes effective if: P036 = 5,
A044 = 3 and ATR is assigned to a digital input and turned on. Re-
fer to MX2 User Manual section 3-9-4.
Note
The Analog Output Channel 1 only becomes effective if: C028 =
16. Refer to MX2 User Manual section 3-7.
Note
A Digital Output only becomes effective if the associated register
(C021, C022 or C026) is set to 63. Refer to MX2 User Manual sec-
tion 3-7.
Note
The Torque Reference only becomes effective if: P033 = 7. Refer
to RX User Manual section 4-3 Torque Control for details.
Note
The Torque Compensation only becomes effective if: P036 = 5.
Refer to RX User manual 4-3 Torque Bias.
Note
The Analog Output Channel 1 only becomes effective if: C028 =
20. Refer to RX User Manual section 4-2 Analogue Output AM/
AMI Terminals.
Note
A Digital Output only becomes effective if the associated register
(C021- C026) is set to 63. Refer to RX User Manual section 4-2
Multi-function Output Terminal Selection.
Table C-3 Ext2 data format I/O mapping
Word Offset
+0
Operation Command
(Section C-4)
+1
Frequency Reference
+2
Modbus
Message Area
+3
(Section C-5)
+4
+5
*1.
Refer to section C-4 Operation Command and Inverter Status Registers on page 80 for the Op-
eration Command and Inverter Status register definitions
Description
0: Stop run forward
0: Stop run reverse
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
Output Area
*1
Inverter Status
Output Frequency
Instruction
Modbus
Message Area
(Section C-5)
Data
Control
Inverter Status
Name
Operation Status
0 Hz Detection
Signal (ZS)
Rotation Direction
Trip Reset Status
Set Frequency Reached
(FA3)
Inverter Ready
Alarm Signal (AL)
APPENDIX C
Input Area
*1
(Section C-4)
Result
Data
Status
Description
1: Inverter is running
0: Inverter is stopped
1: ON
0: OFF
1: Reverse rotation
0: Forward rotation
1: Trip reset (RS) is active
0: Trip reset (RS) not active
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF