Dialer Operation
When only the main dialer is enabled (field 3
output. When both the main and backup dialers are enabled (field 3*30 = 1,1), the panel will Alternate Dialers by pairs
(make two attempts to report on the Main Dialer, then make two attempts to report on the Back Up dialer). The panel
will continue to do this to the Primary Phone number until it reaches its programmed attempts in 3
the same to the Secondary phone number. Test Report is always sent on Alternating dialers
The communicator makes up to 8 attempts to transmit the messages to one or both telephone numbers (primary and
secondary), depending on the report routing options programmed. After the 8
the system displays "COMM FAIL" on the keypad. The number of dialer attempts are programmed in field 3
= 8; must be restricted to 3, 4, or 5 if a secondary phone number is programmed).

Wiring Burglary and Panic Devices to Zones 1-8

The maximum zone resistance is 100 ohms for zones 1, 2 and 8, and 300 ohms for all other zones (excluding the
2K EOL resistor).
To wire burglary and panic devices to zones 1-8, connect sensors/contacts to the hardwire zone terminals (15 through
27). Connect N.C. and N.O. devices as follows:
Connect N.C. devices in series with the high (+) side of the loop. The 2K EOL resistor must be connected in series
with the devices, following the last device.
Connect N.O. devices in parallel (across) the loop. The 2K EOL resistor must be connected across the loop wires
at the last device.
Using 2-Wire Smoke Detectors on Zones 1 and 2
Zone 1 and 2 can support up to 16 2-wire smoke detectors each (32 total).
The alarm current on zones 1 and 2 supports only one smoke detector in the alarmed state.
When assigned zone type 9 or 16, the second entry of a User Code + off at a keypad interrupts power to these zones to
allow detectors to be reset following an alarm.
Compatible 2-Wire Smoke Detectors
For ULC fire installations, 2-Wire Smoke Detectors must not be connected to the fire transmitter. These devices
U LC
must be connected to the Fire Alarm Control Panel.
DETECTOR TYPE
2-Wire Photoelectric Smoke Detector
2-Wire Photoelectric Smoke Detector w/Heat Detector
2-Wire Photoelectric Smoke Detector
2-Wire Photoelectric Smoke Detector w/Heat Detector
2-Wire Ionization Smoke Detector
2-Wire Photoelectric Low-Profile Smoke Detector
Access Reversal Relay/Sync Module
2-Wire Photoelectric Smoke Detector
2-Wire Photoelectric Smoke Detector w/Heat Detector
2-Wire Photoelectric Smoke Detector w/Heat Detector
* This model may not be used on zones designated as Zone Type 16: Fire with Verification.
These smoke detectors are UL Listed for use with the VISTA-128FBPT/VISTA-250FBPT and are the only 2-
wire smoke detectors that may be used.
U L
A combination of heat detectors and smoke detectors is not permitted on a zone programmed for fire
verification.
Fire installations require the use of a synchronization module to synchronize the sounders and strobes on the
system.
30 = 1, 0), the system attempts to route all messages over the main dialer
32
.
attempt, the communicator hangs up and
th
MANUFACTURER
DSC
DSC
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
ESL
ESL
ESL
21, then it will do
21 (default
MODEL #
FSA-210B
FSA-210BT
2W-B
2WT-B
1451 w/B401B base
2151 w/B401 base *
RRS-MOD
521B
521BXT
429AT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-128fbpt

Table of Contents