Close In Alarm/Open In Alarm - Omron E5CSV User Manual

Digital temperature controller
Hide thumbs Also See for E5CSV:
Table of Contents

Advertisement

■ Close in
Alarm/Open in
Alarm
● Summary of
Alarm Operation
When "close in alarm" is set, the status of the alarm function will be
output as is. When "open in alarm" is set, the status of the alarm
function will be reversed before being output.
Close in alarm/open in alarm can be set separately for each alarm.
Close in alarm/open in alarm are set in the "alarm 1 open in alarm"
parameter (initial setting level (4)), and in the "alarm 2 open in
alarm" parameter (initial setting level (5)).
The default is 0 (close in alarm).
Alarm
function
Close in
ON
alarm
OFF
Open in
ON
alarm
OFF
The alarm outputs will turn OFF (i.e., the relay contacts will open)
when power is interrupted and for about two seconds after the
power is turned ON regardless of the close in alarm/open in alarm
setting.
The following figure summarizes the operation of alarms when the
alarm type is set to "lower-limit alarm with standby sequence" and
"close in alarm" is set.
Alarm type: Lower-limit alarm with standby sequence
PV
Alarm
value
Standby sequence
canceled
Alarm
Output
4.3 Alarm Functions
Alarm output
Alarm
function
indicator
ON
Lit
OFF
Not lit
OFF
Lit
ON
Not lit
Alarm hysteresis
ON
OFF
ON (closed)
OFF (open)
Time
4-5