IS mode (2)
Alarm 1 open in alarm
This parameter sets the output status for alarm 1.
When "close in alarm" is set, the status of the alarm 1 function will be output
as is. When "open in alarm" is set, the status of the alarm 1 function will be
Function
reversed before being output.
Alarm 1 open in alarm
Setting
* This parameter is displayed regardless of the output assignment
setting.
* The alarm 1 indicator will display the alarm output function status as is
regardless of the alarm 1 closed in alarm/open in alarm setting.
IS mode (3)
Alarm 1 latch
When this parameter is set to ON, once the alarm 1 function has turned ON it
is held until the power is turned OFF or the latch is cleared.
Function
If the alarm 1 function is set to "close in alarm," the outputs are kept closed. If
they are set to "open in alarm," they are kept open.
When the alarm 1 latch is set to "latch ON" (1), the alarm 1 latch status will be
displayed in the operation level. During operation, the latch clear operation
can be performed in the alarm latch status window.
Setting
* This parameter is displayed regardless of the output assignment
setting.
Parameter
0: Closed in alarm
1: Open in alarm
Parameter
0: Latch OFF
Alarm 1 latch
1: Latch ON
5.7 Initial Setting Level (4)
Setting range
Default
0: Closed in
alarm
Setting
Default
range
0: Latch OFF
nc
lt
5-23