Appendix B. Driver Error Messages

Some configuration errors might produce an error every time a poll is generated. This will fill the
error buffer quickly and not add any clarity. For this reason the driver suppresses subsequent
similar messages. Thus it is possible for the same error produced by multiple Map Descriptors
to produce only one error message. Subsequent error messages can be seen on the driver
message screen.
Note : In the actual message you will see that %d has been replaced by an integer, %s by text
indicating a data array name or map descriptor name and %x by two hex characters.
Error Message
INFRA: #1 Err. Da <%s>
length Reqd/exist <%d/%d>
Md <%s> where md offset
ψ
<%d>
INFRA:#2 Err. Incoming data
is being abandoned on port R-
ψ
P%d
INFRA:#3
ERR.
Node_id %d, Valid 1-8
Infra:#4 Err. Test file <%s> not
found.
INFRA:#11 Err. Illegal MD
ψ
Function for Md <%s>
INFRA:#12 Err. Illegal MD
ψ
length <%s>
INFRA:#13
Err.
Infra_func for Md <%s>
INFRA:#21
Err.
Da
length Reqd/exist <%d/%d>
Md <%s> where md offset
ψ
<%d>
INFRA:#22 Err. Diagnostic line
ψ
<%d> ignored.
INFRA:#41 FYI. Write-thru not
Possible On MD <%s>
Infra:#51 FYI. You could use
an
Array called
<%s>
expose diagnostic info.
ψ
Edit CSV file, download the modified file and reset the FieldServer to have the changes take effect.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
This error will be generated when the driver tries to store data for a
sensor but the corresponding Data Array is not long enough. Set the
Data Array length as indicated..
Honeywell Zellweger IR-148-8.8-Channel or another unit is connected
at the indicated port of the FieldServer but the Configuration file does
not define a Map Descriptor to capture data from this unit. Change the
CSV file to define a Map Descriptor to communicate with this device if
required.
Invalid
If there are multiple nodes then make the Node_ID the number of
points (sensors) for which Zellweger units are configured.
In Simulation mode the driver can send messages from files indicated
by the Map Descriptor name. Check that the required file exists and
that it is not in use by another application, or change the mode from
simulation
"INFRA_SIMULATION" from .the CSV file.
Set Map Descriptor's function to Passive_Client if driver is configured
as a Client or wrbc if configured as a Server.
The Map Descriptor length parameter is either not defined or set to 0.
Set the Map Descriptor length to 100.
Illegal
This error will be generated if you are using the Infra_func parameter
ψ
with an incorrect value. See section 0 for legal values.
<%s>
This error will be generated when the driver tries to send a message to
the Client, but the Data Array used to compose the message is
insufficiently long to hold information for all 8 sensors. Set the Data
Array length as indicated.
In Server mode the driver does not send messages from lines starting
with # or //. Change the Data_Array_Offset parameter for the indicated
line in the ini file.
If an Upstream Device writes a value at a memory location under the
influence of the given Map Descriptor, the Write-thru operation will be
cancelled as the Driver cannot write to an UnfraTox unit..
It is possible to define a Data Array known as "Infra-stats" (see 0) This
to
Data Array is very useful for statistics purposes.
Description and Action Required
to
operation
by
Page 18 of 19
deleting
the
parameter