16 - READ OUT FLOW CHART
CAUTION!!! Changing
these parameters could cause the
boiler and therefore the system to
malfunction. For this reason, only
a qualifi ed technician who has
in-depth knowledge of the boiler
should change them.
The boiler's micro-processor makes
this menu of parameters available to
the qualifi ed technician for the setting
of the appliance .
can assume the follow values:
61 - for boiler at NATURAL gas;
62 - for boiler at LP gas;
can assume the follow values:
00 - 230Vac, 50Hz, °C;
01 - 230Vac, 50Hz, °F;
02 - 120Vac, 60Hz, °C;
03 - 120Vac, 60Hz, °F
To enter this menu you must:
1. turn the main electrical supply Off;
2. move the switch n° 7 (see fi gure
18, item "D") to the ON position;
3. turn the main electrical supply On.
Now "ty" is displayed. Use plus and
minus keys to change the value; use
RESET key to save the value and
swap to the next parameter.
To exit this menu you must:
1. turn the main electrical supply Off;
2. move the switch n° 7 (see fi gure
18, item "D") to the Off position;
76
Basic functionalities selection and Speed blower
selection (see below for more explications)
Main electrical supply and temperature unit
selection (see below for more explication)
Domestic functionalities selection. Must be
always at 00
Master or slave selection in a batterie
confi guration. Must be always at 00.
Rotating selection in a batterie confi guration.
Must be always at 00.
can assume the follow values:
00, 01 and 02. Must be always at 00.
If readable, can assume the follow values:
00, 01, 02, 03, 04, 05, 06, 07 and 08. Must be always
at 00.
If readable, can assume the follow values:
00, 01, 02, 03, 04, 05, 06, 07 and 08. Must be always
at 00.