Installation - Mounting & Gas And Water Connections; Clearances For Installation And Servicing; Clearances From Combustible Material; Choosing The Installation Location - PEERLESS Combi 160 Installation, Operation & Maintenance Manual

Gas boiler
Table of Contents

Advertisement

5 - INSTALLATION - Mounting & gas and water connections
Figure 6 - Recommended minimum clearance
distances for proper installation and servicing
1 = Area for power supply cable
2 = Heating supply connection (3/4")
3 = Domestic hot water connection (3/4")
4 = Gas connection (3/4")
5 = Domestic cold water connection (3/4")
6 = heating return connection (3/4")
7 = positions for boiler support
8 = Flue discharge/air intake connection
Figure 7 - Dimensions for the PC160
5.1 - Clearances for
installation and servicing
Figure 6 shows the clearances required for installation
and servicing.
NOTE: Service clearances are not mandatory, but
are recommended to ensure ease of service should
it be required.
5.2 - Clearances from
combustible material
This boiler may be installed directly onto a wall of combustible
material with the following clearance:
Ceiling:
Front:
Rear:
Sides:
Floor:
Concentric vent: 0 inches (0 mm)
Split vent (fi rst 12" from the boiler): 1 inch (25 mm)
Split vent (after 12" from the boiler): 0 inches (0 mm)
5.3 - Choosing the
installation location
CAUTION!!! The boiler must be installed on a
vertical wall constructed to bear its weight or the boiler
and building may be damaged.
NOTE: The boiler must never be installed on carpeting.
CAUTION!!! This boiler is not designed for direct
outdoor installation. If installed outside of the structure
that it supplies hot water too, it must be sheltered so it is
protected from rain, wind, sun and frost. NEVER place this
boiler in a location that would subject it to temperatures at
or near freezing. Failure to properly locate this boiler can
result in premature failure voiding the warranty.
When locating the boiler the following factors must be
considered:
• the location of vent/air intake terminals;
• connection to the gas supply;
• connection to the water supply;
• connection to the heating system;
• connection to the domestic hot water system;
• connection to the electrical supply;
• disposal of the condensation produced by the boiler;
• connection to the room thermostat;
• piping of the safety relief valve discharge;
• possible connection of the outdoor temperature
sensor;
• possible connection of an indirect storage tank, see
section 7.1.
15
2 inches (51 mm)
2 inches (51 mm)
0 inches (0 mm)
2 inches (51 mm)
2 inches (51 mm)

Advertisement

Table of Contents
loading

Table of Contents