12 - USE
Continued
PARAMETER
DESCRIPTION
Heating service functioning mode
Reaction to external temperature
Angle fulcrum of climatic adjustment
Reduction of temperature generated by
the opening of the room thermostat
Boiler knobs' status
Display "1" and "2" as per fi gure 37
energy saver
Parameter disabled for this kind of boiler
Domestic sensitivity setting
Minimum domestic setpoint during sleep
mode
Proportional band of the heating PID
modulation
Integral of the heating PID modulation
Burner Anticycling: minimum delay from
a burner light-off to the sequent light-on.
Value expressed in sec x 10
INFORMATION ON DISPLAY ITEM "2" OF FIGURE 37
Can be changed:
00 = thermostatic adjustment (see section 12.8);
01 = outdoor reset (see section 12.10);
02 = outdoor reset with room compensation (see section 12.10.6);
Can be changed from 1 to 10 (active only with outdoor reset). See
section 12.10.1 for its adjustment.
Can be changed from 16°F (-9°C) to 149°F (65°C) (active only with
outdoor reset).
See section 12.10.3 for its adjustment.
Can be changed: from 1°F (1°C) to 36°F (20°C) (active only with
outdoor reset featuring room compensation)
See section 12.10.6 for its adjustment.
Can be changed:
01 = knobs presents;
00 = knobs absent.
Can be changed: 00 = display always on; any other value,
corresponds to a delay in the switching off of the display, expressed
in minutes (see also section 12.15)
Can be changed between 1 and 10°F. Default value is 4°F. To
increase the sensitivity set it to 2°F
Can be changed between 104 and 122°F. Default value is 104°F.
Never set domestic setpoint (see section 12.7) at a value lower
than this parameter).
Can be changed between 1 and 99. Default value is 15. Can be
modifi ed only in conjunction with factory technicians.
Can be changed between 1 and 99. Default value is 30. Can be
modifi ed only in conjunction with factory technicians.
Can be changed between 1 and 54. Default value is 18 (180 sec).
Can be modifi ed only in conjunction with factory technicians.