Installation and Setup Guide

Compatible Devices

Device
Addressable Keypads
Touch Screen (AUI)
Devices
4219, 4229 Zone
Expander Modules
5800 Series Wireless
Output relays and/or
Powerline Carrier
Devices (X-10 type)
On-Board Triggers
Output functions
4285/4286 Phone
Module
Audio Alarm
Verification
Alarm output
Auxiliary Power Output
Backup Battery
Long Range Radio
AC Power Supply
NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.

Important Installation Highlights (Installer Please Read)

• This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in
Section 2. Mounting and Wiring – Wiring the Keypads and Other Addressable Devices).
• Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from
previous controls) and programmed in data fields *190-*196.
• Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used.
• 4204 Relay Modules must be set for specific addresses (12-15).
• This control will not power-up unless AC power is connected (will not power-up on battery alone).
However, once the system is powered up, it will operate on battery power in the event of AC loss.
• Relays have two programming menu modes: Use *79 Menu mode to map module addresses and
device (output) numbers. Use *80 Menu mode to define the output functions.
• This system supports programmable function keys. Use *57 Menu mode to define the function
keys.
• This system provides various paging features. Refer to the Programming Overview section for a
summary on pager programming.
1-2
VISTA-20P
VISTA-15P
8
8
2
2
Up to 5 for
Up to 2 for
up to 40
up to 16
exp. zones
exp. zones
Up to 40 RF
Up to 26 RF
zones
zones
Up to 16
Up to 8
2
2
Up to 48
Up to 24
Partition 1
yes
only
Using AAV
Using AAV
module
module
12VDC, 2
12VDC, 2
AMP output
AMP output
See note.
See note
See note.
See note.
See note.
See note.
See note.
See note.
Notes
6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V
Fixed-Word Display Voice Keypad, 6160V Alpha
Display Voice Keypad, 6150RF Keypad/Transceiver
Touch Screen (AUI) devices are in addition to the 8
addressable keypads. E.g., Symphony, 6270
Zone numbers are predefined according to the device
addresses used. See Expander Module Addresses table
in Wiring section and set addresses accordingly.
Uses 5881/5883 Series Receivers/Transceivers.
Use any combination of 4204, 4229 and or Powerline
Carrier Devices.
Map output devices via *79 Menu mode.
Can be used to reset 4-smoke detectors.
Program output functions via *80 Menu mode.
Provides access to the system via on premises or off-
premises phones for arming, disarming, etc., plus
control of relay outputs and Powerline Carrier devices.
Use ADEMCO UVS or Eagle Model 1250; can be used
in conjunction with an output trigger to permit voice
dialog between an operator at the central station and
a person at the premises.
Can drive the compatible sounders; steady output for
burglary/panic, or temporal pulse (3 pulses – pause –
3 pulses – pause – 3 pulses. . .) for fire. Uses current
limiting circuitry for protection.
12VDC, 600 mA maximum; uses fuse for protection.
Rechargeable (sealed lead-acid type) 12VDC, 4AH
minimum.
Primary telephone number messages can be reported
via ECP connection to various Long Range Radios
(check compatibility/availability of specific models)
Plug-in 120VAC transformer, ADEMCO 1321
(1321CN in Canada) or, if using Powerline Carrier
devices, ADEMCO 1361X10 Transformer Module