Enter Zn Num.
(00 = Quit)
10
Zn ZT P RC
In: L
10 00 1 10
RF: 1
OR
Zn ZT P RC
In: AD
10 00 1 10
AW: 07
OR
Zn ZT P RC
HW: RT
10 00 1 10
EL
1
10 Zone Type
Perimeter
03
10 Partition
1
10 Report Code
1st 01 2nd 00 10
02 HARDWIRE TYPE
EOL
0
02 Response Time
1
5-2
Zone Number
VISTA-20P: wired 01-08 (and 09-48†); wireless 09-48; RF button zones 49-64
VISTA-15P: wired 01-06 (and 07-22†); wireless 09-34; RF button zones 49-56
Both Controls: 91 = addr. device report enable; 92 = duress report enable
95, 96, 99 =emerg. zones
[ ∗ ] to continue; 00 to quit
Enter the zone number that you wish to program. Zone 10 has been entered in the example
display at left.
Enter a report code for zone 91 to enable addressable device reporting.
Enter a report code for zone 92 to enable duress reporting.
95, 96, 99 are emergency (panic) key zones.
Summary Screen
[ ∗ ] to continue
A summary display appears.
"IN: L" appears for wireless zones and indicates input type and loop.
"IN: AD" appears for hardwire expansion zones (AW) and indicates the module's address
(AD), which is based on the zone number.
"HW: RT" appears for hardwire zones and indicates configuration (EOL, NO, NC, zone
doubling, double-balanced) and response time selection.
Zone Type (ZT)
See table below.
Each zone must be assigned to a zone type, which defines the way in which the system
responds to faults in that zone. Enter the Zone Type code from the list below:
Note: If 00 is entered, Delete Zone ? will be displayed.
00 = Not used
01 = Entry/exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Day/Night
06 = 24-Hr Silent
*5800 button-type transmitters only
Partition No. (P)
(VISTA-20P)
1-3 = partition (3 = common); [ ∗ ] to continue
Enter the Partition number for this zone. Partition 1 is shown entered.
Report Code (RC)
First Digit: 1-9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F
00 to disable
Second Digit: same as above; [ ∗ ] to continue
Enter the report code for this zone, which consists of 2 hexadecimal digits, each in turn
consisting of 2 numerical digits. For example, for a report code of "10," enter 01 and 00.
For Contact ID®, entering any non-zero entry as the first digit enables the report code for
this zone. Refer to the System Communication section for information about report codes
and formats.
Hardwire Type
0 = EOL; 1 = NC; 2 = NO; 3 = zn doubling
[ ∗ ] to continue
† VISTA-20P
This prompt appears only for zone numbers 02-08.
Zone 1 is automatically set for EOL operation.
Response Time (RT)
0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 seconds; [ ∗ ] to continue
This prompt appears only for hard-wired zones 01-08 (zone 02 is the display shown).
Option 3: used for "clean me" option on zone 1 (see field ∗174).
NOTE: If zone doubling is being used, the response time selected for zones 02-08
automatically applies to each zone's associated doubled zone.
† if zone expanders are used.
07 = 24-Hr Audible
08 = 24-Hr Aux
09 = Fire
10 = Interior w/Delay
12 = Monitor Zone
14 = Carbon Monoxide
16 = Fire w/Verify
†;
4 = dble-balanced (DB)
(ZD)
20 = Arm–STAY*
21 = Arm–AWAY*
22 = Disarm*
23 = No Alarm Resp
24 = Silent Burglary
77 = Keyswitch
81 = AAV Mon. Zone
90-91 = Configurable