Honeywell ADEMCO VISTA-15PSIA Installation And Setup Manual page 47

Ademco vista series
Hide thumbs Also See for ADEMCO VISTA-15PSIA:
Table of Contents

Advertisement

"A"
01 Zn List
1
"B"
01 Enter Zn type
Perimeter
03
"C"
01 Enter Zn No.
12
01 Output Action
Close for 2 sec
1
Zone List
(prompt appears if zone list was selected)
01-08 = zone list; [ ∗ ] to continue
Enter the desired zone list number associated with this output number.
NOTE: Do not use pager zone lists 09-12 in output definitions.
Enter the zone list event that will activate this output.
Enter Event
Alarm
1
NOTE: For alarm, fault, and trouble, an event on ANY zone in the list activates the output,
but ALL zones in the list must be restored before the output is restored.
Press [ ✱ ] to continue and skip to the "Output Action" prompt.
Zone Type
(prompt appears if zone type was selected)
Enter the desired zone type associated with this output number. See below for a list of
available zone types.
CHOICES FOR ZONE TYPES:
00 = Not Used
05 = Day/Night
01 = Ent/Exit #1
06 = 24 Hr Silent
02 = Ent/Exit #2
07 = 24 Hr Audible
03 = Perimeter
08 = 24 Hr Aux
04 = Interior Follower
09 = Fire
10 = Interior w/Delay
CHOICES FOR SYSTEM OPERATION:
20 = Arming–Stay
36 = **At Bell Timeout***
21 = Arming–Away
38 = Chime
22 = Disarming
39 = Any Fire Alarm
31 = End of Exit Time
40 = Bypassing
32 = Start of Entry Time 41 = **AC Power Failure
33 = Any Burglary Alarm 42 = **System Battery Low 67 = Bell Fail
43 = Comm. Failure
** Use 0 (Any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu Mode to assign the function key (function "07").
Note: In normal operation mode:
Code + # + 7 + NN Key Entry starts Device NN.
Code + # + 8 + NN Key Entry stops Device NN.
Enter the partition in which this zone type will occur.
01 Partition
Any partition
0
Press [ ✱ ] to continue and skip to the "Output Action" prompt.
Zone Number
(prompt appears if zone number was selected)
Enter the desired zone number associated with this output number.
Press [ ✱ ] to continue.
Enter the zone event that will activate this output.
01 Enter Event
Restore
0
Press [ ✱ ] to continue to the "Output Action" prompt
Output Action
0 = off
1 = Close for 2 seconds
2 = Stay Closed
3 = Pulse on & off (1 sec ON, 1 sec OFF)
Enter the desired device action as listed above. Press the [ ✱ ] key to continue.
0 = restore; 1 = alarm;
2 = fault; 3= trouble
12 = Monitor Zone
14 = Carbon Monoxide
16 = Fire w/verification
23 = No Alarm Response
24 = Silent Burglary
77 = Keyswitch Zone
81 = AAV Monitor Zone
90-91 = Configurable
52 = Kissoff
54 = Fire Zone Reset
58 = Duress
60 = AAV
66 = Function Key†
68 = Telco Line Cut
78 = Keyswitch Red LED
79 = Keyswitch Green LED
0 = any partition; 1 = partition 1;
2 = partition 2; 3 = common
0 = restore; 1 = alarm/fault/trouble
4 = Change Device State
5 = Duration 1 (see data field *177)
6 = Duration 2 (see data field *177)
Menu Mode Programming
5-11