Design, Assembly and Service Manual
Page 40 of 44
Induction flow meter FMG600 series
any key, preferably
. The basic programming menu will reappear on the display with the "Dose Setting"
item selected.

7.1.9. Zero setting

The zero-setting function is useful in the cases where the actual flow rate is very small (e.g. due to leakage
in closed valves) and for all practical purposes equal to zero. This function can only be used with meters in a
single flow-direction application. Should you open the zero-setting programming mode by mistake (not
wishing to change the zero setting), proceed using the Cancel-Zero setting sequence of commands.
Menu: Zero setting, depress
The display will read "Setting Completed" and show the flow rate as indicated by the meter prior to entry to
the programming mode. Make a note of this value as it cannot be otherwise reconstructed once the new zero
setting has been completed. Depress
. The basic programming menu will reappear on the display with the
"Zero Setting" item selected.
The new zero setting will become effective upon leaving the meter programming mode. At the same time,
three flashing exclamation marks will appear on the display showing the actual flow rate values.
Flowrate
!!!
110.7
m3/h
The flow-rate display image with the zero setting effective
The actual zero setting can be changed at any time by repeating the above "Zero Setting" procedure.
Cancellation of the actual zero flow-rate setting:
Menu: Zero setting, depress
The display will read "Setting Completed" and show the flow rate as indicated by the meter prior to entry to
the programming mode. Depress
. The display will read "Setting Cancelled" while the flow-rate value will
remain unchanged. Depress
. The basic programming menu will reappear on the display with the "Zero
Setting" item selected. The cancellation of zero setting will take effect upon leaving the meter programming
mode. The three flashing exclamation marks on the flow-rate display will disappear.

7.1.10. 100 percent

Default value of the "100 Percent" quantity is Qmax as specified for the sensor DN(see the table of minimum
and maximum flow rates in-section 4.1.1.). This default value can be reset, in particular in cases where the
actual maximum flow rate is lower than Qmax.
Menu: 100 percent, depress
The display will read "100 percent xxxx". Using push-button
move the cursor to the desired decimal
position and increase/decrease the selected figure by push-buttons
and
, respectively. Replace xxxx by
a number equal to the flow rate identified with 100%. Depress
. The display will read "Value entered
Press any key". Press any key, preferably
. The basic programming menu will reappear on the display.

7.1.11. Exit

Select "Exit" to leave the programming mode and protect the meter from any unauthorized programming
action.
Menu: Exit, depress