Deluxe Controls
Troubleshooting equipment contain-
ing the Deluxe Control option may be
made easy by using the three LED's
(light emitting diodes). These LED's
are provided for indicating the oper-
ating mode of the controller. The
LED's are intended to aid in trouble-
shooting and unit maintenance. They
are labeled on the circuit board with
numbers as referenced in Table 6.
GECA-SVX01B-EN
Troubleshooting
Checklist
Table 6: Diagnostic LED's
Color: Green
Color: Red
LED1
LED2
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
FLASH
ON
ON
FLASH
ON
FLASH
ON
ON
ON
ON
ON
FLASH
ON
ON
Controller Mode
LED3
OFF
Control OFF
OFF
Normal/Compressor OFF
FLASH
Anti-short cycle
ON
Normal/Compressor ON
OFF
Brownout condition
ON
Soft Lockout (low pressure)
FLASH
Soft Lockout (high pressure)
ON
Manual Lockout (low pressure)
FLASH
Manual Lockout (high pressure)
OFF
Manual Lockout (condensate overflow)
OFF
Compressor Disable