Table E-2: GECA electrical performance
Model No.
Volts
Total
GECA
FLA
60 HZ
230/60/1
3.5
006
230/60/1
13.2
230/60/1
4.1
009
230/60/1
13.2
230/60/1
17.4
230/60/1
5.7
230/60/1
13.2
012
230/60/1
17.4
230/60/1
6.3
015
230/60/1
13.4
230/60/1
17.6
230/60/1
7.3
018
230/60/1
13.4
230/60/1
17.6
Pump Kit Information
The pump module is a self-contained pumping package for earth-coupled heat pump systems. This kit contains the
components for the operation of a closed-loop earth-coupled heat pump water circuit system. The kit contains:
One Grundfos pump 1/6 HP, 230V, 1PH
Pump rated at 16 GPM at 20-feet of head
3-way brass shut-off valve
Insulated cabinet
See Pump Module Kit manual WSHPC-IN-5 (72-9006-03) for pump module start-up and maintenance.
28
Electrical Requirements
Units w/ Pump Kit
Comp.
Comp.
No. of
Cmp
RLA
LRA
Compr.
MCC
(ea)
(ea)
2.76
17.7
1
2.76
17.7
1
3.40
22.2
1
3.40
22.2
1
3.40
22.2
1
5.00
27.9
1
5.00
27.9
1
5.00
27.9
1
5.40
29.0
1
5.40
29.0
1
5.40
29.0
1
6.40
38.0
1
11.0
6.40
38.0
1
11.0
6.40
38.0
1
11.0
Blower
Blower
Fan
Motor
Motor
Motor
FLA
HP
Num
4.6
0.70
1/20
1
4.6
0.70
1/20
1
6.4
0.70
1/20
1
6.4
0.70
1/20
1
6.4
0.70
1/20
1
8.3
0.70
1/12
1
8.3
0.70
1/12
1
8.3
0.70
1/12
1
9.2
0.90
1/12
1
9.2
0.90
1/12
1
9.2
0.90
1/12
1
0.90
1/6
1
0.90
1/6
1
0.90
1/6
1
Minimum
Overcurrent
Electric Heat
Circuit
Protective
SIZE
Ampacity
Device
5.5
15
None
16.5
20
Min
6.9
15
None
16.5
20
Min
21.7
25
Max
8.4
15
None
16.5
20
Min
21.7
25
Max
9.3
15
None
16.8
20
Min
22
25
Max
10.8
15
None
16.8
20
Min
22.0
25
Max
kW
Amps
0
0
3
12.5
0
0
3
12.5
4
16.67
0
0
3
12.5
4
16.67
0
0
3
12.5
4
16.67
0
0
3
12.5
4
16.67