Introduction The design offers: Another Solution by Trane • Dual sloped plastic drain pan Trane has developed another system • solution to add to their exceptional Hot gas reheat (option) water-source product line. Introducing • Electric heat (option) ™ the Trane Axiom (Model GECA) water- •...
Contents Introduction Model Number Description General Data Features and Benefits Performance Data Sound Control Wiring Dimensional Data Accessories Mechanical Specifications WSHP-PRC004-EN...
General Data Table GD-1 – Physical Data (GECA 006-009) Model: GECA 006-009 Unit Size Length of cabinet (in) [mm] 48 or 63 [1219 or 1600] 48 or 63 [1219 or 1600] Height (in) [mm] 25 or 22 1/2 [635 or 571]...
Features and Benefits Design Advantages The console configuration model GECA product offers a range of capacities ton. This compact HVAC advantage supports multiple application requirements in the commercial conditioning industry. This includes: • Hotel rooms • Offices • Condominiums •...
Page 7
Features and Benefits Field Flexibility Piping and electrical connections to the console are made in either the left or right hand end pocket. The unit refrigeration platform and the unit control box is maintained in the same location whether left or right hand piping, standard unit cabinetry, extended unit cabinetry, or low height unit cabinetry has been specified.
Page 8
Coil specifications for the GECA unit is The insulation in the wet section of the listed below. cabinet complies with ASHRAE standard 62 to accommodate (IAQ) indoor air Table FB-1 –...
Page 9
This platform includes double isolation to the compressor and single isolation to the coaxial water coil. Figure FB-12 – Expansion Valve Expansion Valve All Trane water-source systems include Figure FB-14 – Fan Board Assembly an expansion valve flow metering device. Blower Housing...
Page 10
See fan performance section for factory Figure FB-18 – Bi-directional Registers ratings of low and high speed settings. Supply-Air Registers Supply-air registers for the GECA product are constructed of a plastic, corrosive resistive material. The registers include a snap-in deflection design to...
Page 11
Features and Benefits Sound Attenuation Package The sound package for the console unit The console equipment is designed to includes: achieve the lowest noise levels possible. Table FB-2 – Sound Package Extensive testing has identified the Standard Unit major sound generating sources within Two stage compressor vibration isolation the console unit package.
Page 12
Features and Benefits Cooling Only Units with Electric Heat design, the thermostat is wired directly (option) to the primary electric heat contactor for Electric heat on a cooling only system heating, and the compressor contactor Water incorporates the same nichrome open for cooling.
Page 13
Features and Benefits Hot Gas Reheat (option) For true atmospheric conditioning and climate control, Trane provides accurate, cost effective dehumidification control through a hot gas reheat option. This option is designed to accommodate the size 009 console configuration. With this reheat option, the return air...
Page 14
Features and Basic 24V Benefits Controls Basic 24V Electronic Controls The basic 24V electro-mechanical unit control provides component protection devices for maximum system reliability. Each device, is factory mounted, wired, and tested in the unit. The control package includes: See Figure FB-27 for the console basic 24V control box.
Page 15
Features and Basic 24V Benefits Controls Safety Devices Lockout Relay All unit safety devices are provided to The lockout relay works with the low and prevent compressor damage. high pressure switch to prevent compressor operation if the unit is under Low Pressure Switch low or high refrigerant circuit pressure, The low pressure switch prevents...
Page 16
• Optional: Electric heat conveniently located in the control box. • Optional: Compressor disable input The board is unique to Trane water- source products and is designed to • Optional: Unit mounted controls control the compressor as well as •...
Page 17
Features and Deluxe 24V Benefits Controls Safety Control Deluxe 24V features The deluxe microprocessor receives include: separate input signals from the Random Start refrigerant high pressure switch, low The random start relay provides a time suction pressure switch and condensate delay start-up of the compressor when overflow.
Page 18
Features and Deluxe 24V Benefits Controls Microprocessor Board The application drawing in Figure FB-32 references component device connections to the microprocessor board. Three LED’s (light emitting diodes) are provided for indicating the operating mode of the controller. The LED’s are intended to aid in troubleshooting and unit maintenance.
Page 19
With a multiple unit installation, the units The deluxe 24V electro-mechanical may be daisy-chained directly to the design may be applied as a stand-alone Trane Tracer loop controller (TLC), control system or as a multi-unit pump(s), boiler, and tower for a installation system. With a stand-alone...
Page 20
Features and Tracer ZN.510 Benefits Controls Tracer ZN.510 Controls Tracer ZN.510 is a direct digital control (DDC) system, specifically designed for water-source units to provide control of the entire unit, as well as outputs for unit status and fault detection. Each device, is factory installed and commissioned to ensure the highest level of quality in unit design.
Page 21
Features and Tracer ZN.510 Benefits Controls Data Sharing Tracer ZN.510 features include: The Tracer ZN.510 controller is capable Compressor Operation of sending or receiving data (set points, The compressor is cycled on and off to fan request, or space temperature) to meet heating or cooling zone demands.
Page 22
Features and Tracer ZN.510 Benefits Controls High and Low Pressure Safety Controls Condensate Overflow The Tracer ZN.510 controller detects the When condensate reaches the trip point, state of the high pressure or low a condensate overflow signal generates pressure switches. When a fault is a diagnostic which disables the fan, unit sensed by one of these switches, the water valves (if present), and...
Page 23
Trane’s prevent units from simultaneously Rover ™ service tool .
Performance GECA 006 – Data Cooling – I-P Tabulated performance data is for cooling at 80.6 F [27 C] DB/66.2 F [19 C] WB entering air at ARI-ISO 13256-1 rated CFM. Sensible multipliers vs. entering dry bulb are given at ARI-ISO 13256-1 rating CFM. Multipliers must be used to correct performance at conditions other than those tabulated.
Page 25
Performance GECA 006 – Data Cooling – SI Tabulated performance data is for cooling at 80.6 F [27 C] DB/66.2 F [19 C] WB entering air at ARI-ISO 13256-1 rated CFM. Sensible multipliers vs. entering dry bulb are given at ARI-ISO 13256-1 rating CFM. Multipliers must be used to correct performance at conditions other than those tabulated.
Page 28
Performance GECA 009 – Data Cooling – I-P Tabulated performance data is for cooling at 80.6 F [27 C] DB/66.2 F [19 C] WB entering air at ARI-ISO 13256-1 rated CFM. Sensible multipliers vs. entering dry bulb are given at ARI-ISO 13256-1 rating CFM. Multipliers must be used to correct performance at conditions other than those tabulated.
Page 29
Performance GECA 009 – Data Cooling – SI Tabulated performance data is for cooling at 80.6 F [27 C] DB/66.2 F [19 C] WB entering air at ARI-ISO 13256-1 rated CFM. Sensible multipliers vs. entering dry bulb are given at ARI-ISO 13256-1 rating CFM. Multipliers must be used to correct performance at conditions other than those tabulated.
Page 32
Performance GECA 012 – Data Cooling – I-P Tabulated performance data is for cooling at 80.6 F [27 C] DB/66.2 F [19 C] WB entering air at ARI-ISO 13256-1 rated CFM. Sensible multipliers vs. entering dry bulb are given at ARI-ISO 13256-1 rating CFM. Multipliers must be used to correct performance at conditions other than those tabulated.
Page 33
Performance GECA 012 – Data Cooling – SI Tabulated performance data is for cooling at 80.6 F [27 C] DB/66.2 F [19 C] WB entering air at ARI-ISO 13256-1 rated CFM. Sensible multipliers vs. entering dry bulb are given at ARI-ISO 13256-1 rating CFM. Multipliers must be used to correct performance at conditions other than those tabulated.
Page 36
Performance GECA 015 – Data Cooling – I-P Tabulated performance data is for cooling at 80.6 F [27 C] DB/66.2 F [19 C] WB entering air at ARI-ISO 13256-1 rated CFM. Sensible multipliers vs. entering dry bulb are given at ARI-ISO 13256-1 rating CFM. Multipliers must be used to correct performance at conditions other than those tabulated.
Page 37
Performance GECA 015 – Data Cooling – SI Tabulated performance data is for cooling at 80.6 F [27 C] DB/66.2 F [19 C] WB entering air at ARI-ISO 13256-1 rated CFM. Sensible multipliers vs. entering dry bulb are given at ARI-ISO 13256-1 rating CFM. Multipliers must be used to correct performance at conditions other than those tabulated.
Performance Data Sound The Challenge of Low Sound The GECA product line was developed to be the industry leader in noise performance. To achieve that goal, state of the art acoustic design and test technologies were used to identify and treat the dominant noise and vibration transmission paths in each unit.
Page 44
Performance Data Sound What is Sound Power? What are NC and dBA? Sound power is a measure of the Both NC and dBA are single number acoustical energy emitted from a sound descriptors used to represent perceived source, and is an absolute value. As loudness.
Page 45
No windows • Unit against the short wall (in the middle) Table PD-20 – GECA Rating Summary of NC Sound Pressure Levels For convenience, NC data for all GECA (Sound Attenuation Package) units are provided in Table PD-20. Sound Pressure - NC...
Dimensional Data Clearance Unit Clearance Access to the unit for servicing purposes should be provided at installation. All configurations require clearance from other mechanical and electrical equipment on three service sides (shown below). This enables panel removal from the unit for service/maintenance ability.
Page 50
Dimensional LH Cabinet Std Data Length/Height Left Hand Piping Connection GECA 006-015 1" = 25.4 mm WSHP-PRC004-EN...
Page 51
Dimensional RH Cabinet Std Data Length/Height Right Hand Piping Connection GECA 006-015 1" = 25.4 mm WSHP-PRC004-EN...
Page 52
Dimensional LH Extended Data Length Cabinet Left Hand Piping Connection (Extended Length) GECA 006-015 1" = 25.4 mm WSHP-PRC004-EN...
Page 53
Dimensional RH Extended Data Length Cabinet Right Hand Piping Connection (Extended Length) GECA 006-015 1" = 25.4 mm WSHP-PRC004-EN...
Page 54
Dimensional LH Std Length/ Data Low Ht. Cabinet Left Hand Piping Connection (Low Height Unit) GECA 006-015 1" = 25.4 mm WSHP-PRC004-EN...
Page 55
Dimensional RH Std Length/ Data Low Ht. Cabinet Right Hand Piping Connection (Low Height Unit) GECA 006-015 1" = 25.4 mm WSHP-PRC004-EN...
Page 56
Dimensional LH Chassis Data ONLY Left Hand Piping Connection (Chassis Only) GECA 006-015 1" = 25.4 mm WSHP-PRC004-EN...
Page 57
Dimensional RH Chassis Data ONLY Right Hand Piping Connection (Chassis Only) GECA 006-015 1" = 25.4 mm WSHP-PRC004-EN...
Page 61
Thermostats/ Accessories Sensors Thermostat: X13510575010 Thermostat: X13510586010 Subbase: X13530053010 Auto Changeover Thermostat (Digital) • 2-stage heat/1-stage cool with AUTO- COOL-OFF-HEAT-EM HT • 7-day programmable • Manual Changeover Thermostat Fan switching includes ON-AUTO (Mercury) • 12-degree night set back • 1-stage heat/1-stage cool with HEAT- •...
Page 62
Thermostats/ Accessories Sensors Thermostat: X13510628010 Thermostat: X13510606020 Zone Sensor Zone Sensor • • Tracer ZN.510 and TUC compatible Tracer ZN.510 and TUC compatible • • Internal setpoint External setpoint • • Communication jack Communication jack • ON and CANCEL buttons Thermostat: X13510606010 Thermostat: X13510635010 Zone Sensor...
Page 63
Accessories Options Motorized Water Valve for Open-Loop Hose Kits Accessory Items Systems The basic hose kit consists of a stainless Water Regulating Valve Assembly The motorized water valve is installed on steel outer braid with an inner core or The water regulating valve assembly the return line of the system between the tube made of a non-toxic synthetic consists of a direct acting valve and a...
Mechanical Specifications Sound Attenuation Reversing Valve General Sound attenuation shall be applied as a The reversing valve shall be a pilot Equipment shall be completely standard feature in the product design. operating sliding piston type with assembled, piped, internally wired and replaceable encapsulated magnetic coil.
Page 65
Mechanical Specifications Electrical Terminal Unit Controller Controls The factory tested and installed control This system shall utilize factory furnished Basic Controls box shall contain all necessary devices to and mounted DDC controls for operation The basic control package shall contain a allow heating and cooling operation of of a complete building system on a low and high pressure switch along with...
Page 66
Mechanical Specifications The module shall consist of a single, 1/6- Drain Pan Reheat Coil HP bronze pump, and a brass 3-way The drain pan shall be constructed of Dehumidification shall be provided shutoff valve. These kits shall contain the corrosion resistant material and through a hot gas reheat option.
Page 68
La Crosse www.trane.com For more information contact your local sales office or Since The Trane Company has a policy of continuous product and product data improvement, it reserves e-mail us at comfort@trane.com the right to change design and specifications without notice.
Need help?
Do you have a question about the GECA and is the answer not in the manual?
Questions and answers