Trane GECA -006 Installation Owner Diagnostics page 32

Console configuration water-source comfort system
Table of Contents

Advertisement

Model
Entering
GEVA
Water Temp,
°F
35°
45°
60HZ
55°
018
68°
50 HZ
015
75°
86°
95°
32
Sequence of
Operation
Water
Suction Pres-
Discharge
Flow
sure,
Pressure,
GPM
PSIG
PSIG
3.8
4.8
3.8
73-85
106-138
4.8
74-84
103-133
3.8
74-86
126-162
4.8
75-85
123-159
3.8
75-87
143-185
4.8
75-87
139-179
3.8
75-87
161-207
4.8
75-87
157-201
3.8
76-88
192-246
4.8
76-88
187-239
3.8
77-89
219-281
4.8
77-89
212-272
Operating Data
Cooling
Water
Air Temp
Temp Rise
Drop
°F
°F DB
10-14
23-29
8-12
23-29
9-13
23-29
7-11
23-29
9-13
23-29
7-11
23-29
9-13
22-28
7-11
22-28
9-13
22-28
7-11
22-28
9-13
22-28
7-11
22-28
Heating
Suction
Discharge
Water Temp
Pressure
Pressure
Drop
PSIG
PSIG
°F
37-43
165-207
4-6
38-44
167-209
3-5
48-56
174-220
5-7
50-58
176-222
4-6
57-67
184-232
6-8
60-70
187-235
5-7
71-81
198-250
8-10
74-84
202-254
6-8
78-90
206-260
8-10
82-94
211-265
7-9
91-105
221-277
9-13
95-109
225-283
7-11
GECA-SVX01B-EN
Air Temp
Rise
°F DB
20-26
21-27
23-29
23-31
26-34
26-34
30-38
31-39
32-42
33-43
36-46
37-47