Installation Condition Check; Discharge Pressure Check - Daikin FTX50GV1B Service Manual

Hide thumbs Also See for FTX50GV1B:
Table of Contents

Advertisement

SiBE041029EC
5.9

Installation Condition Check

Check No.17

5.10 Discharge Pressure Check

Check No.18
Service Diagnosis

Installation condition check

Check the allowable
dimensions of the air
suction and
discharge area.
OK
Is the discharged air
short-circuited?
NO
Is the outdoor heat
exchanger very dirty?
NO
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
YES

Discharge pressure check

High?
YES
Is the stop valve open?
YES
Is the connection pipe
deformed?
NO
Is the air
filter or indoor / outdoor
heat exchanger
dirty?
YES
NG
YES
YES
NO
NO
NO
YES
NO
Check
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the outdoor
temperature. (The outdoor
temperature should be
within the operation range.)
Change the installation location
or direction.
(R19401)
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Replace the compressor.
Clean the dirty air filter or
indoor / outdoor heat
exchanger.
(R19385)