Jøtul GF 100 DV II Nordic QT; GF 200 DV II Lillehammer Installation And Operation Instructions Manual page 11

Direct vent gas stove
Table of Contents

Advertisement

Venting Through a Fireplace
Co-linear Vent Installation
This appliance may be vented through a masonry or Class
A prefabricated chimney using a Co-linear Flexible Vent
system approved for use with a solid-fuel burning fire-
place. When installed in the manner described below, this
system can improve the performance of the appliance in
cold climate situations, as well as simplify the vent instal-
lation. See fig. 9.
These installation requirements must be followed:
1. Prior to the installation the chimney flue must be thor-
oughly cleaned and inspected by a qualified chimney
service person.
2. In a masonry chimney, a fireclay liner must be present
the entire length of the chimney.
3. Prefabricated chimneys must be UL 103 or ULC S-629
listed and have a minimum INSIDE diameter of 6
inches, (150 mm).
4. No appliance can be installed into a chimney flue serv-
ing any other appliance of any kind.
5. THE AIR INTAKE FLEX PIPE MUST EXTEND BEYOND THE
DAMPER AREA OF THE FIREPLACE. If the intake flex
duct does not extend the full length of the chimney
and connect to both the unit and the termination cap,
A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED
AND INSTALLED ABOVE THE UNIT PRIOR TO THE END
OF THE INTAKE FLEX AND MUST COMPLETELY SEAL THE
CHIMNEY FLUE FROM THE ROOM.
Consult with the local code authority having jurisdic-
tion before proceeding with this type of installation.
Refer to the vent manufacturer's instructions for
specific installation requirements.
WARNING: FAILURE TO POSITION THE PARTS AND
STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED FOR
USE WITH THIS APPLIANCE, MAY RESULT IN PROPERTY
DAMAGE OR PERSONAL INJURY. BE SURE TO MAINTAIN
THE PROPER CLEARANCES TO COMBUSTIBLES AS DEFINED
IN THIS MANUAL AND IN THE INSTRUCTIONS PROVIDED
WITH EACH VENT COMPONENT.
Exhaust Gas
Max.
Co-linear
Height 15 ft.
(10.66 m)
Min.
Co-linear
Height 8 ft.
(2.44 m)
Air Intake Flex
pipe must
extend above
the damper.
Figure 9.
Co-linear Adaptor installed through a masonry chimney.
Figure 10. Simpson Dura-Vent #923GCL Co-linear Adaptor.
GF 100 DV II:
A : 16 3/4"
GF 200 DV II:
A : 18"
Add 2 1/4" with Long Legs.
Subtract 1" with Plinth
138003_Rev_K / 7.29.10
High Wind
Cap
Intake Air
Sealed
Damper
Max.
Offset 24"
(609 mm)
B
A
B : 20 3/4"
B : 22"
11